Appearance
Y311-010-W/R Remote I/O Module Datasheet

| Y311-010-W | Y311-010-R |
|---|
Reference: Y311-010/020-W/R Technical Manual
Contents
- Overview
- Ordering Information
- Key Features
- Technical Specifications
- Interfaces and Indicators
- Mechanical and Environmental
- Installation and Wiring
- Important Notes
1. Overview
Y311-010 is available in two network variants for the same control point:
Y311-010-W: Wi-Fi version for wireless deployment and mobile commissioningY311-010-R: RJ45 Ethernet version for fixed networks and centralized management
Both models are single-channel remote relay control modules with a 10 A contact rating. The main difference is the network interface and default network settings, while the relay capability, power range, and control logic remain the same.
| Model | DI | DO | Connectivity | Typical Applications |
|---|---|---|---|---|
| Y311-010-W | 0 | 1 x 10 A relay | 2.4 GHz Wi-Fi, AP/STA | Single-light control, pump start-stop, buzzer or beacon alarm, remote reset |
| Y311-010-R | 0 | 1 x 10 A relay | 10/100M RJ45 Ethernet | Single-light control, pump start-stop, buzzer or beacon alarm, remote reset |
2. Ordering Information
2.1 Model Naming
text
Y311 - 0 1 0 - W / R
| | \------ W: Wi-Fi; R: RJ45 Ethernet
| \-------- 010: 0 x DI / 1 x DO / 0 x AI
\----------------- Y311: Remote I/O module family2.2 SKU and Network Capability
| SKU | Description | Connectivity | Interfaces | Power |
|---|---|---|---|---|
| Y311-010-W | 0DI + 1DO, Wi-Fi remote relay module | 2.4 GHz Wi-Fi AP/STA | Power terminal, Wi-Fi antenna, relay terminal, RESET | 7 to 40 VDC |
| Y311-010-R | 0DI + 1DO, Ethernet remote relay module | 10/100M RJ45, static IP or DHCP | Power terminal, RJ45, relay terminal, RESET | 7 to 40 VDC |
2.3 Standard Package
- Y311-010-W or Y311-010-R main unit x1
- Pluggable terminal x1
- Quick-start card x1
- Warranty card x1
The -W version includes a 2.4 GHz antenna by default. The -R version includes Ethernet access guidance.
3. Key Features
- Single
10 ARelay Output: Ideal for lights, solenoid valves, fans, reset loops, and other small to medium loads. - Wi-Fi or Ethernet Versions: Choose
-Wfor wireless access or-Rfor fixed wired networking. - Wide
7 to 40 VDCInput: Fits common industrial12 Vand24 Vpower systems. - Pulse and Timed Control: Supports flash-on, flash-off, and timed relay actions for reset and momentary control.
- Modbus TCP Ready: Standard register access simplifies integration with gateways, SCADA, and cloud platforms.
- Compact Cabinet Installation:
97 x 50 x 32 mmhousing suits terminal boxes, small cabinets, and edge enclosures.
4. Technical Specifications
4.1 Network and Communication
| Parameter | Y311-010-W | Y311-010-R |
|---|---|---|
| Network Interface | 2.4 GHz Wi-Fi | 1 x RJ45, 10/100 Mbps |
| Network Mode | AP / STA | Static IP / DHCP |
| Default Management IP | 192.168.16.254 | 192.168.1.7 |
| Default Port | 60000 (AP) / 10000 (TCP) | 10000 |
| Protocol | Modbus, TCP Server | Modbus, TCP Server |
| Baud Rate | 2400 / 4800 / 9600 / 19200 / 38400 bps | 2400 / 4800 / 9600 / 19200 / 38400 bps |
| Device Address | 0 to 255, broadcast 0xFE supported | 0 to 255, broadcast 0xFE supported |
4.2 Digital Output
| Item | Specification |
|---|---|
| Channel Count | 1 x relay |
| Contact Rating | 10 A @ 30 VDC / 10 A @ 250 VAC |
| Response Time | Operate <10 ms, release <5 ms |
| Control Modes | Manual, flash-on, flash-off, timed |
4.3 Electrical and System
| Parameter | Specification |
|---|---|
| Supply Voltage | 7 to 40 VDC |
| Power Consumption | Standby < 2 W; relay energized < 3.5 W |
| Indicators | PWR, DO1 |
| Reset | Long press to restore default network settings |
5. Interfaces and Indicators
5.1 Interface Definition
| Interface | Y311-010-W | Y311-010-R |
|---|---|---|
V+ / V- | 7 to 40 VDC power input | 7 to 40 VDC power input |
| Wi-Fi Antenna | Standard | Not available |
| RJ45 | Not available | Standard |
COM / NO | Relay output channel 1 | Relay output channel 1 |
RESET | Standard | Standard |
5.2 LED Indicators
| LED | Status | Description |
|---|---|---|
PWR | Solid on / blinking | Solid on = powered; blinking = communication activity |
DO1 | Solid on | Relay energized |
6. Mechanical and Environmental
| Parameter | Specification |
|---|---|
| Dimensions | 97 x 50 x 32 mm |
| Weight | About 180 g |
| Housing | Flame-retardant ABS, IP20 |
| Operating Temperature | -40 to 85 C |
| Humidity | 5 to 95% RH, non-condensing |
7. Installation and Wiring
- Connect a
7 to 40 VDCpower supply and confirm thePWRindicator is normal. - For
-W, connect the device to Wi-Fi. For-R, connect the RJ45 Ethernet cable. - Wire the load to the
COM / NOrelay terminals. - Use the matching configuration tool to set the device address, network settings, and control mode.
- Verify switching through the Modbus commands in the technical manual.
8. Important Notes
Y311-010-WandY311-010-Rare two separate models, not one device with both Wi-Fi and RJ45.- If two relay outputs are required, use
Y311-020-WorY311-020-R. - For inductive loads, add an RC snubber or TVS device to reduce contact arcing.
- Change the default network settings and access password before deployment.
- Manufacturer: Hunan YenGear Tech Co., Ltd.
- Address: Room 21014, Building 1, Fudi Xingguang Tiandi, Yingxin Road, Yuhua District, Changsha, Hunan, China
- Email: [email protected]
- Website: www.yengear.com