Wireless I/O Modules Selection Guide

Use this guide to select a Y401, Y402, Y403, or Y412 Wireless I/O Module by control relationship, I/O count, and operating mode. The Y401/Y402/Y403 modules use a private LoRa link to carry passive dry-contact or NPN open-collector states to SPDT relay outputs; Y412 adds configurable 2-, 4-, and 8-channel master/slave control. No SIM card, Internet connection, or LoRaWAN gateway is required for the basic link. Never apply voltage directly to a DI terminal.

The specified range is up to 10 km in open areas. Treat this as a planning value, not a guaranteed distance: model, antenna, mounting height, obstructions, interference, and local site conditions determine the usable range.

At a Glance

ModelDI / DOControl relationshipBest fitRange*
Y401-11-L1 / 1Point-to-point, bidirectionalOne signal between two fixed locationsUp to 10 km
Y401-22-L2 / 2Point-to-point, bidirectionalTwo independent signals between two locationsUp to 10 km
Y401-44-L4 / 4Point-to-point, bidirectionalFour independent signals between two locationsUp to 10 km
Y402-11-L1 / 1 per nodeOne-to-many, bidirectionalOne controller and several remote pointsUp to 10 km
Y402-44-L4 / 4 per nodeOne-to-many, bidirectionalFour-channel control across multiple pointsUp to 10 km
Y402-4411-L1 master / 4 slaveOne-to-many, 1-to-4 mappingOne trigger drives four remote outputsUp to 10 km
Y403-11-L1 / 1 per nodeMulti-node linkageAny linked node drives all linked outputsUp to 10 km per hop
Y412-22/44/88-L2 / 4 / 8 DI + DOConfigurable master/slaveSelectable unidirectional feedback or bidirectional followUp to 10 km

* Open-area planning value. Confirm the selected model specification and perform a site survey before committing to a range.

Y401 — Point-to-Point I/O Mirroring

Choose Y401 when two fixed locations need corresponding relay actions in both directions. A factory-paired Device A and Device B carry each channel state across the private LoRa link; the remote relay follows the input state.

ModelChannelsTypical selection
Y401-11-L1 DI + 1 DO per nodeDoor contact, pump start/stop, or one remote alarm output
Y401-22-L2 DI + 2 DO per nodeTwo independent switches, valves, or status signals
Y401-44-L4 DI + 4 DO per nodeMulti-channel gate, lighting, or equipment control

Common Y401 facts

  • Point-to-point and bidirectional; no controller, gateway, or software configuration is required for the matched pair.
  • 9–36 VDC module supply; each channel uses a passive DI and an SPDT relay DO.
  • Relay rating: AC 277 V / 5 A or DC 28 V / 5 A. Use an external contactor for larger or inductive loads.

Y402 — One-to-Many I/O Mapping

Choose Y402 when one master location must exchange states with one or more slave locations. Master inputs distribute to the matching slave outputs, while slave inputs can return status to the master.

ModelMaster I/OSlave I/OMapping
Y402-11-L1 DI + 1 DO1 DI + 1 DO per slave1-to-1 channel across multiple slaves
Y402-44-L4 DI + 4 DO4 DI + 4 DO per slaveFour matching channels across multiple slaves
Y402-4411-L1 DI + 1 DO4 DI + 4 DO per slaveOne master input maps to four slave outputs

Common Y402 facts

  • Use one master with one or more factory-paired slaves; the system can be expanded within the product specification.
  • Select Y402-4411-L when one contact must trigger four outputs at each remote point.
  • 9–36 VDC module supply and SPDT relay outputs; relay contacts do not supply load voltage.

Y403 — Multi-Node Linkage

Y403 is a single-model family: Y403-11-L. Choose it when a distributed site needs coordinated auxiliary outputs rather than a single master/slave relationship. Any node input can energize the linked node outputs, and nodes can automatically forward signals to extend the practical path.

FeatureY403-11-L
I/O per node1 DI + 1 DO
Linkage logicAny linked node input → all linked node relay outputs
RangeUp to 10 km per hop in open areas*, with relay paths for coverage extension
Typical useMulti-point linkage alarm, distributed lighting, or coordinated auxiliary equipment control
Reset conditionOutputs reset after all linked node inputs return to open

Y403 is not a certified emergency-stop or personnel-safety system. Keep an independently certified safety path for those functions and validate multi-hop delay for any timing-sensitive control.

Y412 — Configurable Wireless I/O

Choose Y412 when the installation needs a configurable channel count or operating mode rather than one fixed Y401/Y402/Y403 topology. The family is available as 2DI + 2DO, 4DI + 4DO, or 8DI + 8DO, with one master and one or more slave devices configured for the site.

FeatureY412-22/44/88-L
Channel options2, 4, or 8 DI + DO per module
Control modesUnidirectional feedback or bidirectional follow
Output actionMomentary or latching
Power versions8–28 VDC or 85–265 VAC
Relay outputForm A, up to 7 A at 250 VAC or 30 VDC
Typical useAccess-control extension, remote start/stop, pump/valve control, and lighting groups
Range planningUp to 10 km in open areas with the specified antenna and installation conditions*

For DIP settings, wiring, and commissioning, use the Y412 Datasheet and Y412 User Manual.

Select by Application

Application questionRecommended familyWhy
Do two fixed locations need corresponding relay actions?Y401Direct point-to-point I/O mirroring keeps the relationship simple.
Does one control point need to reach several remote points?Y402One-to-many I/O mapping distributes commands and returns status.
Should an input at any of several nodes activate linked outputs?Y403Multi-node linkage forwards the state across the participating nodes.
Does the installation need configurable channel count and operating mode?Y412Select 2/4/8 channels and configure master/slave, direction, and output action.
Is this an emergency-stop, personnel-safety, or hard-real-time loop?None of these wireless modules aloneUse the independently certified safety system; the wireless link may only be auxiliary signalling.

Shared Installation Facts

ItemRequirement
DI inputPassive dry contact or NPN open collector between DI and COM; no voltage input
DO outputY401/Y402/Y403: isolated SPDT relay (NO, COM, NC); Y412: Form A relay (NO, COM); use an external load supply
Module powerY401/Y402/Y403: DC 9–36 V; Y412: 8–28 VDC or 85–265 VAC
AntennaUse the specified band antenna, mount vertically, and keep clearance from large metal surfaces
Range planningUp to 10 km in open areas*; verify antenna, obstruction, interference, and site conditions
Inductive loadsDrive a suitably rated contactor and add surge suppression

Documents

ModelSpecificationShared manual
Y401-11-LOpen specificationWiring and commissioning manual
Y401-22-LOpen specificationWiring and commissioning manual
Y401-44-LOpen specificationWiring and commissioning manual
Y402-11-LOpen specificationWiring and commissioning manual
Y402-44-LOpen specificationWiring and commissioning manual
Y402-4411-LOpen specificationWiring and commissioning manual
Y403-11-LOpen specificationWiring and commissioning manual
Y412-22/44/88-LOpen specificationY412 wiring and commissioning manual

For installation examples, see the Y401 / Y402 / Y403 Application Guide. For the family overview, see Wireless I/O Modules.