Y401 / Y402 / Y403 Wireless I/O Module User Manual

Applicable models: Y401-11-L, Y401-22-L, Y401-44-L, Y402-11-L, Y402-41-L, Y402-44-L, and Y403-11-L.

Product Introduction

The Wireless I/O Module family uses a private LoRa link to replace long-distance control wiring. Each device provides digital input and relay output terminals, so a switch, sensor contact, PLC relay output, alarm contact, or controller contact can be carried, mapped, or forwarded to a remote relay output without a SIM card, Internet connection, or LoRaWAN gateway.

Main features:

  • LoRa wireless communication, 398 to 525 MHz
  • Up to 5 km standard in open areas; a 10 km option is available for selected configurations
  • 9 to 36V DC power input
  • DI supports passive dry contact and NPN open-collector input
  • DO uses SPDT relay output, rated AC 277V / 5A or DC 28V / 5A
  • DIN rail installation

This manual covers shared digital wiring, control logic, pairing, antenna installation, and commissioning. Use the Y401 / Y402 / Y403 Selection Guide for model naming, topology comparison, and model selection. Use each specification for model-specific power, range, relay, and analog-signal limits.

Control Logic

Y401 Point-to-Point

Y401 control diagram

Y401 uses two paired devices: Device A and Device B. When a DI on one device closes, the corresponding DO relay on the other device energizes. When the input opens, the remote relay resets.

Channel mapping:

ModelDevice A InputDevice B OutputDevice B InputDevice A Output
Y401-11-LDI1DO1DI1DO1
Y401-22-LDI1 to DI2DO1 to DO2DI1 to DI2DO1 to DO2
Y401-44-LDI1 to DI4DO1 to DO4DI1 to DI4DO1 to DO4

Y402 One-to-Many

Y402 control diagram

Y402 uses one master and one or more slaves. When the master input closes, the corresponding output on all slaves energizes. When any slave input closes, the corresponding output on the master energizes.

Channel mapping:

ModelMaster to SlaveSlave to Master
Y402-11-LMaster DI1 -> all Slave DO1Any Slave DI1 -> Master DO1
Y402-44-LMaster DI1 to DI4 -> all Slave DO1 to DO4Any Slave DI1 to DI4 -> Master DO1 to DO4
Y402-41-LMaster DI1 to DI4 -> the DO on the assigned one-channel slaveEach slave DI -> the corresponding Master DO1 to DO4

For Y402-11-L and Y402-44-L, the master output resets only after the corresponding input on all slave devices returns to open. For Y402-41-L, each master output follows the input state of its assigned one-channel slave.

Y403 Auto Relay

Y403 control diagram

Y403 uses equal-status nodes in an Auto Relay network. When the DI on any node closes, the DO on all nodes energizes, including the local node. The outputs reset only after every node input returns to open. Nodes automatically relay signals to extend the practical communication path.

For application fit and scenario selection, use the Y401 / Y402 / Y403 Selection Guide. This manual continues with shared installation and commissioning procedures.

Default Parameters

ParameterDefault / Requirement
Wireless modeLoRa
Frequency band398 to 525 MHz
Standard antenna470 MHz magnetic-mount antenna
Power supplyDC 9 to 36V
Input typePassive dry contact / NPN open-collector; no voltage input to DI
Output typeSPDT relay
Relay ratingAC 277V / 5A or DC 28V / 5A
Installation35 mm DIN rail

Note: Wireless delay varies with distance, antenna placement, obstruction, and local interference. These products are not intended for emergency-stop, personnel-safety, hard-real-time, or timing-synchronization loops.

Basic Setup

StepActionDescription
1Identify the architectureUse Y401 for two points, Y402 for master/slave expansion, and Y403 for Auto Relay.
2Install antennasMount antennas vertically and keep them away from large metal surfaces.
3Connect powerUse a certified DC 9 to 36V power supply and observe polarity.
4Check pairingFactory-matched devices can communicate after power-up.
5Wire DI inputsConnect passive dry contacts or NPN open-collector outputs to DI and COM; never apply voltage to DI.
6Wire DO outputsConnect loads or contactor coils through relay terminals NO, COM, and NC.
7Test channel logicClose each input and confirm the expected remote or linked output action.

Hardware Interfaces

Interface AreaTerminal / PartDescription
PowerV+, V-DC 9 to 36V power input
AntennaSMA connectorConnect the supplied LoRa antenna
Digital inputDI, COMContact-closure input for dry contact or NPN open-collector output
Relay outputNO, COM, NCSPDT relay output for load or contactor control
Indicator LEDsPower, link, input, outputShows power, wireless link, DI, and DO status

Relay terminal meaning:

  • COM: common terminal
  • NO: normally open terminal; closes to COM after relay action
  • NC: normally closed terminal; opens from COM after relay action

Wiring notes:

  • Disconnect power before wiring.
  • Never apply voltage to DI terminals.
  • Relay contacts do not output voltage; an external load power supply is required.
  • Add a fuse or circuit breaker according to the load current.
  • For motors, solenoids, contactors, and other inductive loads, add suitable surge suppression.

Pairing and Expansion

Factory-matched devices are already paired. For the Y401, Y402, and Y403 models covered by this manual, use the same three-wire method to pair or re-pair a unit when replacing a unit, adding a Y402 slave or Y403 node, or restoring a lost link.

  1. Power off both units and isolate the loads.
  2. Connect the temporary pairing wires between the two units: position 3 to 4, position 4 to 3, and position 5 to 5. The positions are shown in the pairing diagram; confirm the physical terminal markings on the device.
  3. Connect DC 9 to 36V power to both units, observing polarity.
  4. Power on and wait for both link indicators to remain on.
  5. Power off, remove the temporary pairing wires, then power on and test the wireless control logic.

For Y401, the two units are Device A and Device B. For Y402, use the master and the new or replacement slave. For Y403, use the existing node and the new or replacement node. The three-wire procedure is the same for these three series; confirm the physical terminal markings before connecting.

Y40x three-wire pairing diagram

Antenna Installation

ItemRecommendation
FrequencyUse antennas within 398 to 525 MHz
OrientationInstall vertically
HeightAbout 2 m above ground or higher when possible
ClearanceKeep away from cabinets, walls, pipes, and large metal structures
ConnectorTighten the SMA connector by hand

Good antenna placement improves range more effectively than increasing transmit power. In metal cabinets, lead the antenna outside the cabinet whenever possible.

DI Wiring

DI accepts dry contacts and NPN open-collector outputs. Connect the signal between DI and COM.

No voltage input on DI

Never connect a powered signal or voltage source directly to DI.

Y40x input wiring

For PNP, PLC, or other powered outputs, use an intermediate relay and connect only its dry contact to DI and COM.

DO Wiring Diagrams

DO is an isolated relay contact output. It can switch small loads directly or drive an external contactor for larger loads.

Small Loads

For lamps, alarm devices, small heaters, and other resistive loads within the relay rating, connect the load power line through COM and NO.

Y40x relay output wiring

Contactor-Controlled Loads

Large Loads

Use the module relay output to drive a properly rated contactor for motors, pumps, heaters, and other high-power loads. The contactor switches the load circuit.

Y40x high-power load wiring

Three-Phase Equipment

Use the module relay output to drive a properly rated contactor for three-phase motors, pumps, and other equipment. The contactor switches the three-phase circuit.

Y40x three-phase equipment control wiring

Safety Notes

  • Use a certified power supply and confirm polarity before power-up.
  • Do not install the device in explosive, high-humidity, corrosive, or heavily dusty environments.
  • Do not exceed the relay contact rating.
  • Do not use the wireless link as the only protection path for emergency stop, personnel safety, or other hard real-time safety functions.
  • High-voltage AC wiring must be performed by qualified personnel.