Y301 Serial I/O Modules Selection Guide ​

Y301 serial I/O modules expand digital inputs, relay outputs, analog inputs, or analog outputs over RS485 or RS232. MiniLink and ControlLink use Modbus RTU; FlexPoint modules also list Modbus ASCII support. TTL availability and register maps depend on the model. Use the specification and technical manual for the selected product.

Model Naming ​

Y301 I/O channel code

The positions after Y301- represent DI / DO / AI / AO channel counts on one module. 0 means no channels of that type. Models without AO use three characters for DI, DO, and AI; models with AO retain the fourth position.

CodeChannel count
0–90–9
A10
G16
W32

Interface options are specified separately from the I/O code; use the configuration table in the relevant specification.

ExampleModel interpretation
Y301-2222 DI, 2 DO, 2 AI, and no AO.
Y301-G0016 DI; no DO, AI, or AO.
Y301-00G16 AI; no DI, DO, or AO.
Y301-00044 AO; no DI, DO, or AI.

At a Glance ​

ModelI/ORelay RatingDimensionsLocal Rules
Y301-110Y301-1101DI 1DO125 VAC / 0.5 A77.4 x 22.5 x 16.2 mm2
Y301-200Y301-2002DI-77.4 x 22.5 x 16.2 mm—
Y301-020Y301-0202DO125 VAC / 0.5 A77.4 x 22.5 x 16.2 mm4
Y301-220Y301-2202DI 2DO277 VAC / 10 A82 x 54 x 32 mm4
Y301-222Y301-2222DI 2DO 2AI277 VAC / 10 A82 x 54 x 32 mm4
Y301-440Y301-4404DI 4DO277 VAC / 10 A115 x 90 x 40 mm8
Y301-444Y301-4444DI 4DO 4AI277 VAC / 10 A145 x 90 x 40 mm8
Y301-880Y301-8808DI 8DO277 VAC / 10 A145 x 90 x 40 mm16
Y301-600Y301-6006 DI—120 × 70 × 35 mm—
Y301-800Y301-8008 DI—120 × 70 × 35 mm—
Y301-G00Y301-G0016 DI—120 × 70 × 35 mm—
Y301-006Y301-0066 AI—100 × 70 × 35 mm—
Y301-008Y301-0088 AI—100 × 70 × 35 mm—
Y301-00GY301-00G16 AI—100 × 70 × 35 mm—
Y301-0004Y301-00044 AO—100 × 70 × 35 mm—
Y301-0006Y301-00066 AO—100 × 70 × 35 mm—
Y301-0008Y301-00088 AO—100 × 70 × 35 mm—

Relay ratings also include 30 VDC / 2 A on MiniLink and 28 VDC / 10 A on ControlLink. Match the load voltage, current, and switching duty to the relay rating.

MiniLink provides one or two digital I/O channels in a 77.4 × 22.5 × 16.2 mm enclosure. All three models use 5-36 VDC power.

Y301-110 provides one DI and one relay; Y301-200 provides two DI; Y301-020 provides two relays. Y301-110 supports two local rules and Y301-020 supports four. Y301-200 has no DO and no output rules. Its pulse-counter retention is separate from DO retention, which MiniLink does not support.

ControlLink combines DI and relay outputs. Y301-222 and Y301-444 also include AI. These models use 5-36 VDC power and 277 VAC / 10 A or 28 VDC / 10 A relay contacts.

ModelsDI / DO / AIDimensionsLocal rules
Y301-220 / Y301-2222 / 2 / 0 or 282 × 54 × 32 mm4
Y301-4404 / 4 / 0115 × 90 × 40 mm8
Y301-4444 / 4 / 4145 × 90 × 40 mm8
Y301-8808 / 8 / 0145 × 90 × 40 mm16

Y301-220 has no DIP address offset or output retention. Y301-222, Y301-440, Y301-444, and Y301-880 support a DIP address offset and output retention after a software restart; specify power-cycle retention when ordering if required. Use contactors or load-rated switching equipment where the motor, pump, or other load exceeds the relay's switching limits.

FlexPoint Series ​

FlexPoint expands one I/O type per module. These products use different register maps from MiniLink and ControlLink.

ModelsFunctionSupplySignal options
Y301-600 / Y301-800 / Y301-G006 / 8 / 16 DI7-30 VDCDry contacts or 3.3-24 VDC active inputs
Y301-006 / Y301-008 / Y301-00G6 / 8 / 16 AI7-30 VDC0-10 V or 4-20 mA
Y301-0004 / Y301-0006 / Y301-00084 / 6 / 8 AO12-30 VDC0-10 V or 4-20 mA

Specify the signal mode and interface when ordering. Use the configuration tables for the ordered hardware version.

Series Comparison ​

CriterionMiniLinkControlLinkFlexPoint
I/O arrangementDI, DO, or DI + DODI + DO, with AI on 222/444One I/O type: DI, AI, or AO
Relay contacts125 VAC / 0.5 A; 30 VDC / 2 A277 VAC / 10 A; 28 VDC / 10 ANone on the listed models
Local output rules2 on 110; 4 on 0204, 8, or 16 by modelNot specified
Output retentionNoHardware/firmware-dependentConfigurable on AO versions
Serial interfacesRS485; RS232/TTL optionsRS485; RS232/TTL optionsRS485/RS232

Documents ​

ModelSpecificationUser ManualTechnical Manual
Y301-110/200/020SpecificationUser ManualTechnical Manual
Y301-220/222SpecificationUser ManualTechnical Manual
Y301-440/444SpecificationUser ManualTechnical Manual
Y301-880SpecificationUser ManualTechnical Manual
Y301-600/800/G00SpecificationUser ManualTechnical Manual
Y301-006/008/00GSpecificationUser ManualConfiguration reference in specification
Y301-0004/0006/0008SpecificationUser ManualConfiguration reference in specification