Skip to content

Y305-JJ00 PLC I/O Module Specification ​

Y305-JJ00 PLC I/O module

User Manual · Technical Manual · All Y305 models

1. Overview ​

Y305-JJ00 runs local PLC programs with 18 digital inputs and 18 digital outputs. It has no analog inputs or outputs. The four code positions represent DI / DO / AI / AO; E represents 14 channels and J represents 18.

2. Ordering information ​

Relay outputs are the default; NPN transistor outputs are a separate hardware option, not a software setting. RTC (real-time clock) is standard. Specify the output hardware, RS485 port count, and any high-speed counting or pulse requirements when ordering. Availability depends on the hardware combination. Relay outputs cannot generate high-speed pulses.

3. Technical specifications ​

ParameterSpecification
Nominal supply24 VDC; obtain the permitted range, consumption and inrush for the supplied unit
Digital inputs18; S/S to +24 V, with a dry contact or compatible sinking signal from Xn to 0 V
Digital outputs18; relay by default, NPN optional
Input / output labelsX0–X7, X10–X17, X20–X21 / Y0–Y7, Y10–Y17, Y20–Y21; verify against the delivered unit drawing
Analog inputs / outputsNone
Relay loadStated ceiling: 5 A at AC 220 V or DC 30 V, subject to load conditions
NPN loadStated ceiling: 3 A; obtain the output voltage and load ratings for the ordered hardware
ProgrammingGX Works2 with an FX3U-style device/instruction model; use the setup specified for the hardware and firmware
RTCStandard; clock accuracy, backup duration and power-loss recovery require verification
CommunicationUp to two optional RS485 ports; Modbus RTU master/slave or non-protocol RS communication

The output ceilings do not establish continuous per-channel, common-terminal, inductive-load, inrush, or simultaneous-load ratings. Obtain the applicable ratings before connecting loads. NPN outputs are for DC loads only. Match sensors to the input thresholds, current, filter and leakage limits. RS and ADPRW cannot operate simultaneously.

4. Dimensions and installation ​

ParameterValue
Enclosure, width × height × depth185 × 108 × 49 mm
Relay PCB outline, two edge lengths182.00 × 96.00 mm

PCB edge lengths do not specify enclosure orientation. Use the drawing for the delivered hardware to locate mounting holes, terminals and clearances; do not use PCB dimensions as a drilling template.

Select the enclosure and installation site using the unit's environmental, protection, isolation and EMC limits. Do not use Y305 as a safety PLC or sole protective control. Provide independent safety functions where required. Test startup, STOP, power loss and communication recovery with loads isolated; do not assume an automatic safe output state. See the User Manual for installation.