Y401 / Y402 / Y403 Wireless I/O Module Selection Guide ​

Use this guide to select a Y401, Y402, or Y403 Wireless I/O Module by control relationship and I/O type. Digital Y401/Y402/Y403 models use a private LoRa link to carry passive dry-contact or NPN open-collector states to relay outputs. Y401-99-L is a 9DI/9DO DC-powered model; Y401-0011-L and Y401-0044-L are point-to-point analog models with no DI or DO channels. No SIM card, Internet connection, or LoRaWAN gateway is required for the basic link. Never apply voltage directly to a digital DI terminal.

Standard versions of the listed models use a planning range of up to 5 km in open areas. A 10 km range option is available for selected configurations with the specified antenna and installation conditions. The standard Y401-99-L supports up to 5 km with clear line of sight and has no 10 km option. Fast communication versions of Y401-11-L and Y401-99-L have a communication distance of 1000 m and latency below 500 ms. Treat every range as a planning value, not a guaranteed distance: model, antenna, mounting height, obstructions, interference, and local site conditions determine the usable range.

Model Naming ​

Y401 / Y402 / Y403 model naming

Y401, Y402, and Y403 models use the -ABCD-L suffix. The four positions encode I/O counts, and L identifies LoRa communication. Their control modes are:

ModelControl mode
Y401One-to-one
Y402One-to-many
Y403Auto Relay
PositionMeaning
ASender DI / DO channel count
BReceiver DI / DO channel count
CSender AI / AO channel count
DReceiver AI / AO channel count
LLoRa communication

Each count applies to both the input and output type on that side: 1 in a digital position means 1 DI and 1 DO. 0 means no channels of that type. Digital-only models use AB, with the trailing analog digits omitted.

For analog models, confirm the actual AI and AO channel counts in the dedicated specification. The Y401-0011-L hardware specification defines one AI and one AO channel per device.

Sender and receiver identify the two sides of the link; bidirectional devices can both send and receive. For Y402, these sides are the master and slave. Y403 uses equal-status nodes that automatically select a communication path and forward signals.

ExampleModel interpretation
Y401-11-LOne-to-one LoRa pair; each device has 1 DI and 1 DO.
Y402-41-LOne-to-many LoRa system; the master has 4 DI and 4 DO, and each slave has 1 DI and 1 DO.
Y403-11-LAuto Relay LoRa network; each node has 1 DI and 1 DO.
Y401-0011-LOne-to-one LoRa analog pair; neither side has digital I/O, and each device has 1 AI and 1 AO.

At a Glance ​

ModelDI / DOControl relationshipBest fitRange*
Y401-11-L1 / 1Point-to-point, bidirectionalOne signal between two fixed locationsStandard: up to 5 km; 10 km option. Fast version: 1000 m, less than 500 ms
Y401-22-L2 / 2Point-to-point, bidirectionalTwo independent signals between two locationsUp to 5 km; 10 km option
Y401-44-L4 / 4Point-to-point, bidirectionalFour independent signals between two locationsUp to 5 km; 10 km option
Y401-99-L9 / 9Point-to-point, bidirectionalNine-channel control between two locationsStandard: up to 5 km with clear line of sight. Fast version: 1000 m, less than 500 ms
Y402-11-L1 / 1 per nodeOne-to-many, bidirectionalOne controller and several remote pointsUp to 5 km; 10 km option
Y402-44-L4 / 4 per nodeOne-to-many, bidirectionalFour-channel control across multiple pointsUp to 5 km; 10 km option
Y402-41-L4-channel master / 1-channel slaveOne-to-many, 4-to-1 mappingFour master channels reach up to four one-channel remote pointsUp to 5 km; 10 km option
Y403-11-L1 / 1 per nodeAuto RelayAny linked node drives all linked outputsUp to 5 km per hop; 10 km option

* Open-area planning value. Confirm the selected model specification and perform a site survey before committing to a range.

Y401 — Point-to-Point I/O Mirroring ​

Choose Y401 when two fixed locations need corresponding relay actions in both directions. A factory-paired Device A and Device B carry each channel state across the private LoRa link; the remote relay follows the input state.

ModelChannelsTypical selection
Y401-11-L1 DI + 1 DO per nodeDoor contact, pump start/stop, or one remote alarm output
Y401-22-L2 DI + 2 DO per nodeTwo independent switches, valves, or status signals
Y401-44-L4 DI + 4 DO per nodeMulti-channel gate, lighting, or equipment control
Y401-99-L9 DI + 9 DO per nodeHigh-channel remote control, equipment status, or alarm signalling

Analog Y401 Models ​

ModelChannels per nodeSignalTypical selection
Y401-0011-L1 AI + 1 AO4-20 mAOne analog signal between two fixed locations
Y401-0044-L4 AI + 4 AO4-20 mA or 0-10 VFour analog signals between two fixed locations

These analog Y401 models have no DI or DO channels. Use their dedicated specifications for signal wiring, power, range, and the ordered signal configuration.

Common digital Y401 facts

  • Point-to-point and bidirectional; no controller, gateway, or software configuration is required for the matched pair.
  • Y401-11-L, Y401-22-L, Y401-44-L, and Y401-99-L use DC 9–36 V module power.
  • Y401-11-L and Y401-99-L are also available as fast communication versions: 1000 m communication distance and latency below 500 ms. Specify the required version when ordering.
  • Digital inputs use passive dry contacts or NPN open-collector signals. Y401-99-L provides 9 DI and 9 relay output channels per module.
  • Relay ratings are model-specific. Y401-99-L is rated at AC 250 V / 5 A or DC 28 V / 5 A; use an external contactor for larger or inductive loads.

Y402 — One-to-Many I/O Mapping ​

Choose Y402 when one master location must exchange states with one or more slave locations. Master inputs distribute to the matching slave outputs, while slave inputs can return status to the master.

ModelMaster I/OSlave I/OMapping
Y402-11-L1 DI + 1 DO1 DI + 1 DO per slave1-to-1 channel across multiple slaves
Y402-44-L4 DI + 4 DO4 DI + 4 DO per slaveFour matching channels across multiple slaves
Y402-41-L4 DI + 4 DO on master1 DI + 1 DO per slaveEach master channel maps to one assigned one-channel slave

Common Y402 facts

  • Use one master with one or more factory-paired slaves; the system can be expanded within the product specification.
  • 9–36 VDC module supply and SPDT relay outputs; relay contacts do not supply load voltage.

Y403 — Auto Relay ​

Y403 is a single-model family: Y403-11-L. Any node input can energize the linked node outputs, and the Auto Relay network can forward signals to extend the practical path.

FeatureY403-11-L
I/O per node1 DI + 1 DO
Linkage logicAny linked node input → all linked node relay outputs
RangeUp to 5 km per hop in open areas*; 10 km option available, with relay paths for coverage extension
Normal reset conditionDuring normal communication, outputs reset after all linked node inputs return to open

Y403 is not a certified emergency-stop or personnel-safety system. Keep an independently certified safety path for those functions and validate multi-hop delay for any timing-sensitive control.

Communication Loss ​

For the Y401, Y402, and Y403 digital relay models, if wireless communication is lost, the receiver retains the last relay output states for approximately 80 seconds. If communication has not recovered by then, the relay outputs automatically reset to the de-energized (OFF) state. The normally open (NO–COM) contacts open.

This relay timeout does not define the analog output fault state of Y401-0011-L or Y401-0044-L. Their datasheets leave that behavior undefined; follow the dedicated analog specifications.

Shared Digital Installation Facts ​

The following requirements apply to the digital relay models. For Y401-0011-L and Y401-0044-L, follow the analog wiring diagrams and limits in the dedicated specification.

ItemRequirement
DI inputPassive dry contact or NPN open collector between DI and COM; no voltage input
DO outputY401/Y402/Y403 digital models: isolated SPDT relay (NO, COM, NC); use an external load supply
Module powerY401-11/22/44-L, Y402, and Y403: DC 9–36 V; Y401-99-L: DC 9–36 V
AntennaUse the specified band antenna, mount vertically, and keep clearance from large metal surfaces
Range planningStandard versions: up to 5 km; 10 km option for selected configurations, excluding Y401-99-L. Fast versions of Y401-11-L and Y401-99-L: 1000 m, latency below 500 ms. Verify antenna, obstruction, interference, and site conditions
Load selectionObserve both voltage and current ratings for the selected model; use the model-specific AC rating and DC 28 V / 5 A rating rather than a fixed power threshold
Inductive loadsDrive a suitably rated contactor and add surge suppression

Documents ​

ModelSpecificationUser Manual
Y401-11-LOpen specificationWiring and commissioning manual
Y401-22-LOpen specificationWiring and commissioning manual
Y401-44-LOpen specificationWiring and commissioning manual
Y401-99-LOpen specificationWiring and commissioning manual
Y401-0011-LOpen specificationWiring and commissioning manual
Y401-0044-LOpen specificationWiring and commissioning manual
Y402-11-LOpen specificationWiring and commissioning manual
Y402-44-LOpen specificationWiring and commissioning manual
Y402-41-LOpen specificationWiring and commissioning manual
Y403-11-LOpen specificationWiring and commissioning manual

For the family overview, see Wireless I/O Module.