Skip to content

Y402-41-L LoRa One-to-Four Wireless I/O Module System Specification ​

Y402-41-L MasterY402-41-L Slave
Y402-41-L master imageY402-41-L slave image

Contents ​

  1. Overview
  2. Ordering Information
  3. Key Features
  4. Technical Specifications
  5. Interfaces and Indicators
  6. Mechanical and Environmental
  7. Installation and Wiring
  8. Important Notes

1. Overview ​

Y402-41-L links a 4DI/4DO master with up to four 1DI/1DO slaves over LoRa. Each one-channel slave exchanges signals with one assigned master channel.

Y402-41-L control diagram

Operating Logic ​

  • Master to slave: when master DI1 to DI4 is closed, the DO on the slave assigned to that channel energizes
  • Slave to master: when a slave DI is closed, the corresponding DO1 to DO4 on the master energizes
  • The corresponding master and slave outputs reset when the associated input returns to open
  • Four independent channels provide bidirectional transmission between the master and assigned one-channel slaves

Channel Mapping ​

Master channelAssigned slaveMaster-to-slaveSlave-to-master
Channel 1One 1DI/1DO slaveMaster DI1 -> slave DOSlave DI -> master DO1
Channel 2One 1DI/1DO slaveMaster DI2 -> slave DOSlave DI -> master DO2
Channel 3One 1DI/1DO slaveMaster DI3 -> slave DOSlave DI -> master DO3
Channel 4One 1DI/1DO slaveMaster DI4 -> slave DOSlave DI -> master DO4

Communication Loss ​

If wireless communication is lost, the receiver retains the last relay output states for approximately 80 seconds. If communication has not recovered by then, the relay outputs automatically reset to the de-energized (OFF) state. The normally open (NO–COM) contacts open.

2. Ordering Information ​

System Components ​

DeviceModelRoleChannels
MasterY402-41-LCentral control unit4DI/4DO
SlaveY402-41-LRemote terminal unit1DI/1DO

System configuration:

  • Basic system: 1 master + 1 slave (factory paired)
  • Expanded system: 1 master + up to 4 slaves, with each slave assigned to one master channel

Model Configuration ​

Y402-41-L is a one-to-many LoRa system. The first digit, 4, specifies 4 DI and 4 DO on the master; the second digit, 1, specifies 1 DI and 1 DO on each slave.

For the full code and examples, see Model Naming.

Package Contents ​

Qty.Item
1Y402-41-L master module
1Y402-41-L slave module
2470 MHz magnetic-mount antennas
2DIN rail clips
1Quick reference guide
1Warranty card

3. Key Features ​

  • Passive dry-contact/NPN inputs and SPDT relay outputs
  • Reverse-polarity protection
  • Private LoRa communication without a SIM card or Internet gateway

4. Technical Specifications ​

Wireless ​

ParameterSpecification
Frequency band398 to 525 MHz
Communication modeHalf-duplex
Communication rangeUp to 5 km standard; 10 km option available for selected configurations
Antenna connectorSMA
Standard antenna470 MHz magnetic-mount antenna

Electrical ​

ParameterSpecification
Supply voltage9 to 36V DC
Max. power consumption1.5W (master) / 0.8W (slave)
Master inputs4 x passive dry contact / NPN open-collector (no voltage input to DI)
Master outputs4 x SPDT relay
Slave input1 x passive dry contact / NPN open-collector (no voltage input to DI)
Slave output1 x SPDT relay
Output ratingAC 277V 5A / DC 28V 5A
Operating temperature-20 to +85 degC
Operating humidity10% to 90% RH, non-condensing

5. Interfaces and Indicators ​

Master Interfaces ​

InterfaceDescription
AntennaSMA connector for LoRa antenna
PowerDC 9 to 36V input with reverse-polarity protection
Input4 x passive switch inputs (DI1 to DI4 + COM)
Output4 x relay outputs (NO + COM + NC)

Slave Interfaces ​

InterfaceDescription
AntennaSMA connector for LoRa antenna
PowerDC 9 to 36V input with reverse-polarity protection
Input1 x passive switch input (DI + COM)
Output1 x relay output (NO + COM + NC)

LED Indicators ​

DeviceLEDFunctionStatus
MasterPowerSystem statusOn after power-up
MasterLink 1 to 4Channel link statusOn when the corresponding channel link is established
MasterInput 1 to 4Input statusOn when the corresponding DI is closed
MasterOutput 1 to 4Output statusOn when the corresponding relay is energized
SlavePowerSystem statusOn after power-up
SlaveLinkChannel link statusOn when the wireless link is established
SlaveInputInput statusOn when DI is closed
SlaveOutputOutput statusOn when the relay is energized

6. Mechanical and Environmental ​

Mechanical Specifications ​

ParameterMasterSlave
Dimensions88 x 72 x 59 mm88 x 37 x 59 mm
WeightApprox. 50 gApprox. 50 g
Mounting35 mm DIN rail35 mm DIN rail
Protection ratingIP20IP20
Housing materialFlame-retardant plasticFlame-retardant plastic

7. Installation and Wiring ​

Use the Y402-41-L user manual for power, input, and relay wiring, pairing or replacement, and commissioning.

DI accepts dry contacts or NPN open-collector signals, not voltage inputs. Relay contacts require an external load supply. Select the load and protection against the electrical ratings above.

8. Important Notes ​

  • Range figures assume an open-area installation. The 10 km option requires the specified configuration and antenna; obstructions, interference, and antenna placement affect the installed link.
  • The half-duplex wireless link is unsuitable for guaranteed timing or as the sole emergency-stop/personnel-safety path.
  • Use one master per system. Each master channel serves one assigned one-channel slave, up to four slaves in total.

  • Manufacturer: Hunan YenGear Tech Co., Ltd.
  • Address: Room 21014, Building 1, Fudi Xingguang Tiandi, Yingxin Road, Yuhua District, Changsha, Hunan, China
  • Email: [email protected]
  • Website: www.yengear.com