Y403-11-L Auto Relay Wireless I/O Module User Manual ​

Y403-11-L front view with power terminals, signal connections, status indicators, and SMA antenna connector

Product Introduction ​

Applicable model: Y403-11-L.

Y403 links equal-status LoRa nodes, each with 1 DI and 1 relay DO. An input at any node controls the outputs on every linked node. Nodes forward signals to extend the communication path. No gateway or Internet connection is required.

Use the linked model specifications for dimensions and technical ratings, and the Selection Guide for model comparison.

Operating Logic ​

Channel Mapping ​

Two Y403-11-L Auto Relay modules

Y403 uses equal-status nodes in an Auto Relay network. When the DI on any node closes, the DO on all nodes energizes, including the local node. During normal communication, the outputs reset only after every node input returns to open. Nodes automatically relay signals to extend the practical communication path.

Communication Loss ​

If wireless communication is lost, the receiver retains the last relay output states for approximately 60–120 seconds. If communication has not recovered by then, the relay outputs automatically reset to the de-energized (OFF) state. The normally open (NO–COM) contacts open. This timeout is separate from the normal input-following logic.

Installation and Wiring ​

The cover shows Y403-11-L. Identify terminals from the device markings and the applicable model specification. Input COM and relay COM serve different circuits.

Power Wiring ​

Disconnect module and load power before wiring. Connect each module's marked power + and − to a regulated 9–36 V DC supply. Check polarity before power-up.

Antenna Installation ​

  1. Connect the supplied matching antenna before power-up and tighten the SMA connector by hand.
  2. Mount the antenna vertically, about 2 m above ground where possible, clear of metal structures and outside metal cabinets.
  3. Mount the module on a 35 mm DIN rail inside a suitable enclosure. Leave space for wiring and ventilation. Check each planned relay path when positioning Y403 nodes.

Input Wiring ​

Connect a dry contact between DI and input COM. For an NPN open-collector output, connect its collector to DI and emitter or 0 V reference to input COM. Power the sensor separately according to its rating.

Dry-contact and NPN input connections

No voltage input on DI

Do not connect sensor power or a voltage-output signal directly to DI. Use an intermediate relay for PNP or other powered outputs, and connect only its dry contact to DI and COM.

Output Wiring ​

When the relay energizes, NO–COM closes and NC–COM opens.

The relay contacts supply no voltage. Wire the external load supply and load in series through relay COM and NO for normally open operation. Fit overcurrent protection and surge suppression for the load.

Small Loads ​

Y403 relay output wiring

Keep a directly switched resistive load within both contact limits: 5 A at 277 V AC or 5 A at 28 V DC. Use a suitably rated external contactor or power relay for high-power or inductive loads; the module relay switches its coil.

Contactor-Controlled Loads ​

Large Loads

The contactor switches the equipment load; the module switches the contactor coil.

Y403 high-power load wiring
Three-Phase Equipment

Use a three-phase contactor to switch the motor circuit.

Y403 three-phase equipment control wiring

Pairing and Configuration ​

To add or replace a node, use an existing network node and the new or replacement Y403-11-L node. Pair them with the three-wire procedure. Nodes have equal status.

  1. Power off both units and isolate the loads.
  2. Connect the temporary pairing wires between the two units: position 3 to 4, position 4 to 3, and position 5 to 5. The positions are shown in the pairing diagram; confirm the physical terminal markings on the device.
  3. Connect each unit to its 9–36 V DC supply, observing polarity.
  4. Power on and wait for both link indicators to remain on.
  5. Power off, remove the temporary pairing wires, then power on and test the wireless control logic.

Y403 three-wire pairing connections

Commissioning ​

Initial Setup ​

Before applying power, check the model, channel assignments, pairing, antennas, power polarity, and signal/load wiring. Keep control loads isolated during the functional checks.

LED Indicators ​

LEDStatus
Work / PowerOn after power-up
LinkOn when the wireless link is established
InputOn when the corresponding DI is closed
OutputOn when the corresponding relay is energized

Functional Checks ​

  1. Isolate the control loads, connect antennas, and power the linked nodes.
  2. Close DI on one node and confirm that DO energizes on every node, including that local node.
  3. Close DI on a second node, then open the first node DI. During normal communication, all outputs must remain energized while any node DI remains closed.
  4. Open every node DI and confirm that all outputs reset. Repeat the trigger test from each installed node.
  5. Check communication at every final node location and along the intended relay path. With loads isolated, verify the communication-loss reset before connecting control loads.

Troubleshooting ​

SymptomChecks
No wireless linkCheck power at each unit, antenna connections and placement, and the supplied pairing or completed pairing procedure.
Input indicator does not turn onCheck the dry contact or NPN open-collector connection between DI and COM. Do not apply a voltage signal to DI.
Relay action does not match the expected inputCheck DI on every linked node, including the local node. During normal communication, all outputs reset only when every DI is open.
Relay operates but the load does notCheck NO/COM/NC selection, the external load supply, wiring, protection devices, and load ratings. Relay contacts do not supply voltage.
Intermittent communication or timeout resetCheck antenna clearance, obstructions, interference, and power at the final locations. Isolate control loads while checking the communication-loss behavior.

Safety Notes ​

  • Use a certified power supply and confirm polarity before power-up.
  • Do not install the device in explosive, high-humidity, corrosive, or heavily dusty environments.
  • Do not exceed the relay contact rating.
  • Do not use the wireless link as the only protection path for emergency stop, personnel safety, or other hard real-time safety functions.
  • High-voltage AC wiring must be performed by qualified personnel.