Y305 PLC I/O Modules Specification: Y305-4400/4421/8800/8821 ​

Y305 PLC I/O modules run local control programs and provide either 4 digital inputs and 4 digital outputs or 8 of each. Y305-4421 and Y305-8821 add two 0–10 V inputs and one 0–10 V output.

User Manual · Technical Manual · Documentation Index

Contents ​

  1. Model selection
  2. Electrical specifications
  3. Programming and interfaces
  4. Dimensions
  5. Installation limits

1. Model selection ​

ModelDigital inputs (DI)Digital outputs (DO)Analog inputs (AI)Analog outputs (AO)
Y305-44004400
Y305-44214421
Y305-88008800
Y305-88218821

The four positions after Y305 represent DI / DO / AI / AO. A zero means no channels of that type; the AO position remains present when it is zero.

SelectionOrdering information
Output hardwareRelay by default; DC NPN transistor optional. Specify this separately from the four-digit model.
RS485Specify whether RS485 is required and whether one or two ports are needed. The model code does not specify port count.
RTCSpecify whether clock functions are required; availability depends on the selected hardware combination.
High-speed counting or pulse outputSpecify the signals, channels, and rates required. Use only hardware rated for those functions; relay outputs cannot generate high-speed pulses.

Match the order record to the delivered options. Relay and NPN outputs are different hardware, not a software setting. Analog channels on 4421/8821 are voltage channels; they do not provide direct current-loop, thermocouple, or RTD inputs.

2. Electrical specifications ​

2.1 Supply and digital inputs ​

ParameterValue
Nominal module supply24 VDC
DI count4 on 4400/4421; 8 on 8800/8821
Input arrangementS/S to +24 V; a dry contact or compatible sinking signal connects Xn to 0 V
Channel labelsX0–X3 or X0–X7

24 VDC is the nominal supply, not a permitted voltage range. Obtain the unit's supply tolerance, current consumption, and inrush before sizing the supply. Match powered sensors to the DI thresholds, input current, filter time, and leakage limits. Do not apply AC to supply or DI terminals.

2.2 Digital outputs ​

ParameterRelay hardwareNPN transistor hardware
Output actionSwitches a contact circuitSinks DC load current
Stated load voltageAC 220 V or DC 30 VUse the output-voltage rating for the ordered hardware
Stated current ceiling5 A, subject to the load conditions below3 A, subject to the load conditions below
AC loadsSubject to the applicable contact/load ratingProhibited
High-speed pulse outputNot supported through relay contactsRequires channel-specific hardware ratings
Channel labelsY0–Y3 or Y0–Y7Y0–Y3 or Y0–Y7

These figures alone do not establish a per-channel continuous-load rating or a common-terminal rating. They do not define motor or inductive-load capability, inrush, or simultaneous channel loading. Obtain the applicable load-category, common-terminal, and derating ratings before connecting a load. Use a rated interposing device where direct switching is unsuitable; its input or coil must also meet the PLC output rating.

2.3 Analog I/O: Y305-4421 and Y305-8821 ​

ParameterValue
Channels2 AI + 1 AO
Signal range0–10 V
Raw range / resolution0–4095 / 12 bits
Input terminalsAD0, AD1
Output terminalDA0
Signal referenceGND, wired to the unit's reference arrangement

Nominal voltage = raw value × 10 / 4095. Resolution is not an accuracy specification. Match sensors and receivers to the unit's accuracy, update time, AI impedance, AO load capability, and reference/isolation limits. Do not apply an external voltage to DA0 or connect 4–20 mA directly to these channels.

For measurement registers and scaling, see the Analog and PID Guide.

3. Programming and interfaces ​

ItemDescription
Local controlUser PLC program
Engineering softwareGX Works2 programming with an FX3U-style device/instruction model; use the setup specified for the hardware and firmware
RS485 optionUp to two fitted ports; Modbus RTU master/slave or non-protocol RS communication
Network integrationAn external gateway can connect an RS485 bus to a network; select it for the required protocol and application

RS and ADPRW cannot operate simultaneously. Protocol settings and register access are in the Technical Manual; connection and transaction workflows are in the Modbus Integration Guide.

4. Dimensions ​

Digital sizeModelsEnclosure, mmRelay PCB outline, mm
4 DI + 4 DOY305-4400 / Y305-442196 × 99 × 4192.50 × 87.00
8 DI + 8 DOY305-8800 / Y305-8821125 × 99 × 41122.80 × 87.80

Enclosure dimensions are width × height × depth. PCB outlines are the two edge lengths in the relay drawings; their order does not indicate enclosure orientation. Use the drawing for the delivered hardware to locate mounting holes, terminals, and required clearances; do not use PCB dimensions as enclosure dimensions or as a drilling template.

5. Installation limits ​

Select the enclosure and installation site using the unit's environmental, protection, isolation, and EMC limits. Product certification requirements must match the intended installation.

Do not use Y305 as a safety PLC or as the sole protective control. Provide independent safety functions where required. Test startup, STOP, power loss, and communication recovery with production loads isolated; do not assume an automatic safe output state. Installation steps are in the User Manual.