Y305 PLC I/O Modules Technical Manual
Applies to Y305-4400, Y305-4421, Y305-8800, and Y305-8821. PLC devices and special registers address program data, analog I/O, serial communication, and clock functions. Hardware options determine which physical functions are available.
Isolate actuators before writes or program transfer. Use the User Manual for wiring and the Programming Guide for the first program.
Specification · User Manual · Documentation Index
Contents
- Program and output control
- PLC devices and instructions
- Analog registers and scaling
- RS485 configuration
- Modbus addresses and data
- ADPRW and RS instructions
- High-speed functions and RTC
- PID parameters
1. Program and output control
Use GX Works2 with the software version, project settings, interface, and instruction set specified for the unit. An FX3U-style device name does not guarantee identical behavior to another PLC.
A Y-device write or D8050 write can operate a physical output. Direct host writes can also conflict with PLC logic. Application command registers, interlocks, acknowledgment, and timeouts are program-defined, not a factory command interface. Use the Modbus Integration Guide when designing that interface.
2. PLC devices and instructions
2.1 Device areas
| Area | Function | Limit to check |
|---|---|---|
| S | State relays, ordinary and retained | Obtain the firmware-specific upper device boundary |
| X | Digital inputs | Physical count follows the hardware; terminal labels use octal-style numbering |
| Y | Digital outputs | Only fitted channels exist; pulse output requires suitable transistor hardware |
| M | Internal relays, ordinary, retained, and special | Address range and special-device side effects |
| T | Timers: 100 ms, 10 ms, 1 ms, and accumulating groups | Time base, instruction behavior, and retention |
| C | Counters, including 32-bit and high-speed groups | Width, input assignment, and retention |
| D | Data and special-function registers | Ordinary and special D have separate Modbus regions |
| V/Z | Index registers V0–V7 and Z0–Z7 | Required instruction behavior |
Documented D areas are D0–D199 and D600–D7999 for ordinary data, D200–D599 for retained data, and D8000–D8150 for special retained data. Other documented retained areas are S512–S911, M512–M1535, C100–C199, and 32-bit C200–C255. Obtain the unit's retention method, retention duration, and write-endurance limits; test power-loss recovery before relying on retained data.
Allocate application data only in an ordinary region supported by the target firmware. Communication, analog, clock, and other special registers are not scratch storage. Use explicit initialization where the application must start with known values.
2.2 Timer groups
| Timer range | Nominal time base | Type |
|---|---|---|
| T0–T199 | 100 ms | Ordinary |
| T200–T245 | 10 ms | Ordinary |
| T246–T249 | 1 ms | Accumulating |
| T250–T255 | 100 ms | Accumulating |
| T256–T511 | 1 ms | Ordinary |
Select the time base before calculating a preset. Accumulating behavior is not a guarantee of retention through power loss. Check reset and restart behavior on the target firmware; scan and I/O delays affect the observed event timing.
2.3 Instructions
Documented instruction families include basic logic, set/reset and edge operations, jumps/subroutines, transfer/compare, integer and floating-point arithmetic, shift/rotate operations, timers/counters, serial communication, PID, clock operations, high-speed counting, and pulse/positioning.
Check the firmware-supported instructions and data types. Test execution order, scan timing, arithmetic limits, and required instruction behavior before integrating with live equipment.
3. Analog registers and scaling
| Signal | Register | Access | Nominal raw range |
|---|---|---|---|
| AD0 | D8030 | Read input | 0–4095 |
| AD1 | D8031 | Read input | 0–4095 |
| DA0 | D8050 | Write output | 0–4095 |
These channels apply to Y305-4421 and Y305-8821. Y305-4400 and Y305-8800 have no analog channels.
- Voltage = raw × 10 / 4095.
- Raw output target = desired voltage × 4095 / 10, rounded to an integer using the application's chosen rule.
- Clamp output commands to 0–4095 before writing D8050.
- Engineering value = minimum + raw × (maximum − minimum) / 4095 for a linear transducer spanning 0–10 V.
The ideal raw value at 5 V is 2047.5, so an integer command must use a defined rounding rule. The nominal step is about 2.442 mV. Neither value specifies measurement accuracy. Set acceptance tolerances from the unit's accuracy specification. Check overrange diagnostics and calibration requirements, and keep AO writes within range.
Check the sensor's transfer function and fault signals. A low reading does not necessarily represent a valid zero. See the Analog I/O and PID Guide for scaling and loop tests.
4. RS485 configuration
4.1 Registers and flags
| Device | Function |
|---|---|
| D8120 | Port 1 communication format |
| D8400 | Port 2 communication format |
| D8121 | Modbus station address; documented initial value 1 |
| D8129 | Communication timeout, ms |
| D8412 | ADPRW retry count |
| M8029 | Instruction completion |
| M8063 | Serial communication error |
| M8409 | Timeout indication |
| M8121 | RS send-wait flag |
| M8122 | RS send request |
| M8123 | RS receive-complete flag |
| M8124 | RS carrier-detect flag |
| M8161 | RS 8-bit processing mode |
| D8122 | RS remaining transmit count |
| D8123 | RS receive-count monitor |
| D8124 / D8125 | RS header / trailer |
| D8063 | Serial communication error code |
Before using two ports, check how D8121 and D8129 apply to each port, their permitted values, whether settings persist, and when changes take effect. Hardware configurations provide up to two RS485 ports.
4.2 Format word
| Bits | Field | Documented values |
|---|---|---|
| 0 | Data length | 1 = 8 bits; other values unspecified |
| 2:1 | Parity | 00 = none; 01 = odd; 11 = even |
| 3 | Stop bits | 0 = 1; 1 = 2 |
| 7:4 | Baud code | Codes listed below |
| 8 | Header | 0 = absent; 1 = present, RS mode using D8124 |
| 9 | Trailer | 0 = absent; 1 = present, RS mode using D8125 |
| 12:10 | Reserved | Leave at the verified value |
| 13 | Additive checksum | 0 = absent; 1 = added, RS mode only |
| 14 | Protocol | 0 = Modbus; 1 = non-protocol RS |
| 15 | Role | 0 = slave in Modbus mode; 1 = master |
| Baud code, hexadecimal | Bit rate, bit/s |
|---|---|
| 1 | 300 |
| 4 | 600 |
| 5 | 1200 |
| 6 | 2400 |
| 7 | 4800 |
| 8 | 9600 |
| 9 | 19200 |
| A | 38400 |
| B | 56000 |
| C | 57600 |
| D | 115200 |
Verify the selected bit rate on the target firmware. Do not substitute a conventional baud-code sequence for these documented assignments.
4.3 Configuration examples
| Format word | Interpretation |
|---|---|
| H0081 | Modbus slave, 9600 bit/s, 8 data bits, no parity, 1 stop bit |
| H8081 | Modbus master, 9600 bit/s, 8 data bits, no parity, 1 stop bit |
| HC081 | Non-protocol RS, bit 15 set, 9600 bit/s, 8N1 |
H81 and H0081 denote the same hexadecimal value. Read the current serial settings before connecting; these examples do not specify factory settings. The example MOV K300 D8129 sets a 300 ms timeout; set the required timeout explicitly. Select timeout and retries for the slave's response time and the application's failure handling.
RS and ADPRW cannot run simultaneously under the documented restriction. Check the firmware's port-routing procedure. Test each port and the required simultaneous operation before connecting two buses.
5. Modbus addresses and data
5.1 Address convention
Modbus raw protocol addresses differ from the one-based offsets and 4xxxx reference labels that some host tools display. Select the host convention explicitly before entering an address.
Bit and register addresses occupy separate spaces. The function code determines which space a request accesses. A D register does not become an input register because it contains an input measurement.
5.2 Register and bit anchors
| PLC device | Modbus space | Raw decimal | Raw hexadecimal |
|---|---|---|---|
| X0 | Read-only bit input | 1024 | 0x0400 |
| Y0 | Read/write bit output | 1280 | 0x0500 |
| M0 | Read/write bit | 2048 | 0x0800 |
| D0 | Holding register | 4096 | 0x1000 |
| D8000 | Special holding register | 3072 | 0x0C00 |
These are documented anchor addresses. Read function codes, X/Y numbering beyond the anchors, and target-firmware access still need tests. Keep physical outputs isolated for write tests and avoid competing host/PLC writes.
| Analog register | Derived raw decimal | Derived raw hexadecimal | Calculation |
|---|---|---|---|
| D8030 / AD0 | 3102 | 0x0C1E | 3072 + 30 |
| D8031 / AD1 | 3103 | 0x0C1F | 3072 + 31 |
| D8050 / DA0 | 3122 | 0x0C32 | 3072 + 50 |
The analog offsets are derived from the D8000 anchor and require bench verification. Do not address D8030 as 4096 + 8030. The special D region uses a separate base.
The documented D8000 region is a holding-register space. FC03 is the standard read candidate, subject to target-firmware testing. Do not choose FC04 solely because AD0 is an analog input.
5.3 Access limits and data layout
Use the firmware-specific address map for block transfers, timer/counter values, 32-bit counters, and special relays. Start with single known addresses rather than scanning the complete PLC device space. Special-register writes can change communication or drive outputs.
Select a function supported by the addressed device. Master instruction examples below use FC04 (read input registers), FC06 (write single register), and FC16/0x10 (write multiple registers); master and slave support must be checked separately. Test required reads/writes, quantity limits, broadcasts, exceptions, and illegal-address responses on the intended firmware.
Check signedness per value, RS buffer byte packing, multi-register word order, and floating-point representation with a known test pattern. Standard Modbus wire rules do not establish how the PLC packs 32-bit values. The Modbus Integration Guide covers address checks and transaction handling.
6. ADPRW and RS instructions
6.1 ADPRW examples
These instruction fragments illustrate an input-register read and single- and multiple-register writes. Test them on the intended hardware and firmware before use.
| Fragment | Operation |
|---|---|
MOV H8081 D8120 | Configure port 1 as Modbus master, 9600 bit/s, 8N1 |
MOV K300 D8129 | Set a 300 ms timeout; choose the operating timeout for the actual slave |
ADPRW H2 H6 H0A K0 D0 | Station 2, FC06, remote raw address 0x000A, local data at D0 |
ADPRW H2 H10 H0A K5 D1 | Station 2, FC16/0x10, write five registers from remote raw address 0x000A using D1–D5 |
ADPRW H2 H4 H0 K2 D10 | Station 2, FC04, read two input registers from remote raw address 0 into D10–D11 |
K0 in the single-register example is the documented instruction-specific quantity convention for FC06; it is not a zero-register wire request. Keep that operand when reproducing the example, and test the complete transaction on the target firmware. The remote address belongs to the target slave and is not automatically Y305's address for D10.
These fragments omit ladder execution conditions. Add a tested trigger, completion, and error sequence before use, and prevent unintended repeated writes. They are not complete runnable programs. Use the transaction scheduler to prevent competing requests.
6.2 RS example
For this port-2 example, configure port 1 as slave and port 2 as master. Port 1 has documented sending priority when it remains master. Verify the selected physical port before transmitting; do not carry over a port-1 master configuration from the ADPRW example.
| Fragment | Meaning |
|---|---|
MOV H0C081 D8400 | Configure port 2 for non-protocol RS, bit 15 set, 9600 bit/s, 8N1 |
MOV H306 D0 | First word of the illustrated transmit buffer |
MOV H0 D1 | Second buffer word |
MOV H1 D2 | Third buffer word |
CRC D0 D3 K6 | Calculate CRC for the six-byte payload using this instruction convention |
SET M8122 | Request transmission |
RS D0 K8 D100 K8 | Send eight bytes from D0; receive up to eight bytes into D100 |
RST M8123 | Clear the receive-complete flag |
H0C081 and HC081 are the same hexadecimal value. The intended payload is 03 06 00 00 00 01, followed by two CRC bytes: a write of value 1 to station 3, FC06, raw register address 0. This operates a remote register; it is not a read-only connection test.
The fragments omit the complete ladder sequence. Establish M8161 mode, word-to-byte packing, CRC placement/order, and received-length behavior before use. Do not assume RS supplies Modbus framing automatically. The short example sets M8122 during initialization; it does not show how to request each subsequent send. A periodic call to RS alone does not establish continuous transmission.
Use the RS send/wait/validate sequence to handle repeated requests and replies. RS and ADPRW cannot operate simultaneously, including when different ports are selected.
7. High-speed functions and RTC
7.1 High-speed counter inputs
| Counter | Documented input assignment |
|---|---|
| C235 | X0, single phase |
| C236 | X1, single phase |
| C237 | X2, single phase |
| C238 | X3, single phase |
| C239 | X4, single phase |
| C240 | X5, single phase |
| C251 | X0/X1, A/B pair |
| C253 | X3/X4, A/B pair |
| C255 | X6/X7, A/B pair |
Y305-4400/4421 expose X0–X3; Y305-8800/8821 expose X0–X7. These assignments are usable only where both the input and high-speed hardware are fitted. Allocate each input to one counter function. Use the input-frequency rating for the ordered hardware, signal type, counting mode, and simultaneous channel use. M8198 selects four-times counting in two-phase operation. Enable the counter through tested PLC logic and check direction, scaling, rollover, and restart behavior.
Do not use an L low-speed unit for high-speed counting or pulse output without channel-specific hardware ratings.
7.2 Pulse outputs
Y0/Y1 are the documented pulse-output assignments for suitable transistor hardware. Use the frequency and load ratings for the ordered configuration. Do not infer Y2/Y3 pulse capability from positioning-register names. Check channel count, waveform limits, shared resources, and instruction restrictions for the unit. Relay outputs cannot perform high-speed pulse positioning.
7.3 RTC registers
| Register | Field |
|---|---|
| D8013 | Seconds |
| D8014 | Minutes |
| D8015 | Hours |
| D8016 | Day |
| D8017 | Month |
| D8018 | Year |
| D8019 | Weekday |
RTC hardware is optional. Use the unit's field encoding, weekday convention, year range, and setting procedure. Check coherent reads, backup duration, and power-loss recovery before using time-based control. Follow the firmware instructions for TRD/TWR before writing clock registers.
8. PID parameters
The PID operand form is PID S1 S2 S3 D: S1 is the target, S2 is measured feedback, S3 starts a ten-register parameter block, and D receives the result.
| Relative register | Example base D20 | Parameter |
|---|---|---|
| S3 | D20 | PID channel number, listed 0–4 |
| S3+1 / S3+2 | D21–D22 | KP, floating-point |
| S3+3 / S3+4 | D23–D24 | KI, floating-point |
| S3+5 / S3+6 | D25–D26 | KD, floating-point |
| S3+7 | D27 | Error coefficient/threshold KE |
| S3+8 | D28 | Upper output limit PMAX |
| S3+9 | D29 | Lower output limit PMIN |
This ten-register layout is implementation-specific. Do not substitute another PLC's PID parameter block. Execution period, gain units, numeric encoding, initialization, anti-windup behavior, and sensor-failure response need tests before closed-loop operation.
S2 must contain live measured feedback. A fixed feedback value can cause integral saturation and abnormal control. Scale target and feedback consistently and bound the output.
D is the program-selected destination. Choosing D8050 drives DA0 directly. During commissioning, calculate into a verified ordinary D register, check and clamp the result, then transfer it to D8050 through the output-control logic. Keep the plant disconnected until simulated or limited-energy loop tests pass. See the Analog I/O and PID Guide for the test procedure.
8.1 Remote-feedback example
On a unit with RS485 and analog output fitted, the instruction fragments below read an external instrument and calculate a local AO command. Feedback comes over Modbus, rather than from AD0 or AD1.
| Fragment | Meaning |
|---|---|
MOV H8081 D8120 | Port 1, Modbus master, 9600 bit/s, 8N1 |
ADPRW H1 H3 H0 K1 D10 | Slave 1, FC03: read one holding register from raw address 0 into D10 |
PID D0 D10 D20 D8050 | Setpoint D0, feedback D10, parameter block D20–D29, result to D8050 |
This PID fragment writes the physical analog output. Calculation channels 0–4 are not five physical analog outputs; Y305-4421/8821 each have one AO. During commissioning, use ordinary D scratch storage for the result, then validate, limit, and map the command through the final output-control path.
The example's numeric setpoint and gains do not specify physical units or recommended tuning. The source initializes floating-point gains with DEMOV; do not substitute single-word integer values or a different PLC's parameter format.
The accompanying initialization uses these values. They explain the operand allocation and are not tuning defaults:
| Initialization fragment | Meaning |
|---|---|
MOV K400 D0 | Example setpoint 400, with no defined engineering unit |
MOV K0 D20 | PID calculation channel 0 |
DEMOV E500 D21 | KP = 500.0, occupying D21–D22 |
DEMOV E0.1 D23 | KI = 0.1, occupying D23–D24 |
DEMOV E0 D25 | KD = 0.0, occupying D25–D26 |
MOV K3 D27 | KE = 3 in the example's error scale |
MOV K4095 D28 | PMAX = 4095 |
MOV K0 D29 | PMIN = 0 |
Reserve the complete D20–D29 block before loading any of these values. DEMOV denotes the floating-point move shown in this example; its two-word destination must not overlap other data. Check control direction, gain units, and execution timing before choosing parameters for an actual process.
A read and PID call triggered by the same timer can use the previous feedback value. Wait for a valid transaction result, check measurement age, and scale the value before accepting it as new feedback. A nominal timer interval does not define the PID algorithm's internal sampling period. See the remote-feedback control sequence.