Y301 ControlLink Series Serial I/O Modules User Manual ​

Applicable models: Y301-220, Y301-222, Y301-440, Y301-444, Y301-880.

Product Overview ​

ControlLink modules are serial I/O modules with digital inputs (DI), relay outputs (DO), and optional analog inputs (AI). They connect via RS485 using Modbus RTU.

Key features:

  • Integrated DI and DO on all models
  • RS485 standard; RS232 and TTL available on selected models
  • 5-36 VDC power supply
  • Dry and wet contact DI support
  • Relay outputs for valves, lights, alarms, and contactors
  • AI on Y301-222 and Y301-444; order the voltage or current terminals required by the sensor
  • DIN-rail or screw mounting

Model Naming ​

Y301 I/O channel code

The positions after Y301- represent DI / DO / AI / AO channel counts on one module. 0 means no channels of that type. Models without AO use three characters for DI, DO, and AI; models with AO retain the fourth position.

CodeChannel count
0–90–9
A10
G16
W32

Interface options are specified separately from the I/O code; use the configuration table in the relevant specification.

For example, Y301-220 has 2 DI and 2 DO with no analog I/O; Y301-222 adds 2 AI. Y301-444 has 4 DI, 4 DO, and 4 AI. All ControlLink models listed in this manual have no AO.

Model Selection ​

ProductModelDIDOAIDocumentation
Y301-220Y301-220220More Details
Y301-222Y301-222222More Details
Y301-440Y301-440440More Details
Y301-444Y301-444444More Details
Y301-880Y301-880880More Details

Default Parameters ​

ParameterDefault Value
Communication protocolModbus RTU
Device address1
Baud rate9600 bps
Data bits / Stop bits / Parity8 / 1 / None
Power supply5-36 VDC

Note: Each RS485 device must have a unique address. Changes to address or baud rate require a restart. If communication fails, verify address, baud rate, A/B polarity, and GND connection.

Hardware Interfaces (Y301-444 Example) ​

The following uses Y301-444 (4 DI, 4 DO, 4 AI) as an example.

Interface AreaTerminalDescription
Power+, -5-36 VDC; use the terminal labels on the supplied module
CommunicationA, B, GNDRS485 terminals
DI InputDI1-DI4, COM/COM-, COM+Inputs, common reference, and supply positive
DO OutputCOMn, NOn, NCnY301-220/222/440/444 relay contacts; Y301-880 has COMn / NOn only
AI InputVn+, In+, AIn-Voltage positive, current positive, and signal return; n = channel number
DIP SwitchSW1~SW5Address offset; see technical manual
Reload ButtonReload / ResetRestore defaults or restart

DO terminal definitions (where fitted):

  • COM: Common
  • NO: Normally open (closes when relay on)
  • NC: Normally closed (opens when relay on)

Wiring precautions:

  • Power off before wiring
  • Use shielded twisted pair for RS485; add 120Ω termination at both ends of long runs
  • Add flyback diodes, RC snubbers, or surge protection for inductive loads
  • Relay rating: 277 VAC / 10 A or 28 VDC / 10 A

Wire colours: positive (+) red, negative (-) black, RS485 A yellow, and RS485 B green. Identify each connection by its terminal label.

Power and Serial Wiring ​

Disconnect power before changing connections. The terminal drawings show electrical connections, not the physical order of the connector pins. Use only the serial interface fitted to the ordered module.

DC Power ​

Connect a 5-36 VDC supply to + and -.

5-36 VDC module power wiring

RS485 ​

Connect host A to module A, B to B, and the signal reference to GND. On a combined label, TX/A is A and RX/B is B. Use a twisted pair for A/B, a line topology, and 120-ohm termination at the two physical ends of a long bus.

RS485 A B GND wiring

RS232 or TTL Variants ​

Cross TX and RX and connect GND to GND. Use an adapter with the same electrical interface as the module. Confirm the fitted TTL logic voltage before connection; RS232 and TTL require different adapters.

RS232 or TTL transmit receive crossover wiring

DI Wiring Diagram ​

The DI excitation / active signal range is 5-36 VDC. Use the circuit for the terminal arrangement on the module; a DI common and a relay common are different terminals.

ModelInput terminalsDry-contact circuit
Y301-220 / Y301-222COM, DI1-DI2Single COM
Y301-440COM, DI1-DI4Single COM
Y301-444COM+, COM-, DI1-DI4Separate COM+ / COM-
Y301-880Input COM1 for DI1-DI4; input COM2 for DI5-DI8Two input banks

Dry Contact - Common Terminal ​

For Y301-220/222/440 and each Y301-880 input bank, the shared dry-contact circuit connects supply positive to the input common and each contact between its DI and supply negative. In the shared drawings, COM(n) means COM on Y301-220/222/440, or the bank common on Y301-880: input COM1 for DI1-DI4 and input COM2 for DI5-DI8. These input commons are separate from the relay COM terminals. Use the separate polarity shown below for an active signal.

Shared common-terminal dry-contact wiring

Dry Contact - COM+ / COM- ​

For Y301-444, COM+ provides module supply positive. Connect the contact between COM+ and its DI, and connect COM- to supply negative.

Y301-444 COM plus COM minus dry contact wiring

Wet Contact Input ​

Connect active signal positive to DI and signal negative to its input COM / COM-. On Y301-880, use the input common for that bank. Supply the module through its DC terminals. Leave Y301-444 COM+ unused in this active-signal circuit.

Single COM active input wiring

Y301-444 active input wiring

## DO Wiring Diagram

Relay contacts require an external load supply. The drawings use a low-voltage load; select protection and suppression for the actual load and relay contact rating. Module DC power and load power are separate connections.

Y301-220 / 222 / 440 / 444 ​

Route load supply through COMn and NOn for normally-off operation. NCn is available for normally-on operation on these models; it is unused in the illustrated COM/NO load circuit.

Three terminal ControlLink relay wiring

Y301-880 ​

Each output exposes COMn and NOn only; no NC terminal is exposed.

Y301-880 normally open relay wiring

AI Wiring Diagram ​

Y301-222 and Y301-444 provide AI. Select the ordered input range and use one signal type per channel. Leave the unused voltage or current positive terminal disconnected.

Voltage Input ​

For a 0-10 V source, connect signal positive to V1+ and signal return to AI1-.

ControlLink voltage input wiring

Current Input - Powered Source ​

For a powered 4-20 mA source with a separate signal pair, connect signal positive to I1+ and signal return to AI1-. Power the source according to its specification.

ControlLink powered current source wiring

Current Input - Two-Wire Transmitter ​

Connect loop supply positive to transmitter positive, transmitter negative to I1+, and AI1- to loop supply negative. Choose the loop supply for the transmitter and input burden; it is not a module power-output terminal.

ControlLink two wire current loop

Three-Wire Sensor ​

Connect sensor supply positive to its power input. Connect sensor GND, supply negative, and AI1- together. Connect sensor OUT to V1+ for the fitted voltage range, or I1+ for the fitted current range.

ControlLink three wire analog sensor

---