Y811-95AV — Seven-Color Sounder-Beacon Technical Manual
This manual covers the Y811-95AV seven-color sounder-beacon. Sections 4-8 describe the Modbus RTU protocol documented by the manufacturer for the RS485 version. Use the Y811-95AV specification as the authority for the ordered supply, protection rating, dimensions, mounting, and interface option.
1. Safety and scope
Y811-95AV provides auxiliary audible and visual warning. It is not an emergency-stop circuit, a certified fire-alarm panel, a life-safety system, or a safety-rated control circuit.
The manufacturer manual lists a rated supply of DC 12-40 V and calls for a DC supply with a rated current of at least 1 A. Do not connect AC power or more than 40 V to a DC version. The catalog also lists an AC 220 V option; only qualified personnel may install an AC version. Disconnect power before wiring, mounting, opening the light cover, or replacing audio files.
2. Product parameters
| Parameter | Manufacturer value |
|---|---|
| Rated supply | DC 12-40 V |
| Control | Modbus RTU over RS485, or three switch inputs; the catalog and wiring diagram also list RS232 |
| Light colors | Red, yellow, green, white, blue, cyan, purple |
| Light patterns | Steady, slow flash, rapid flash |
| Audio output | 10 W (12 V supply, 8 Ω speaker) |
| Sound level | 0-100 dB |
| Audio format | MP3, bit rate up to 192 kbps |
| Frequency response | 70 Hz to 13 kHz |
| Audio memory | 8 MB built-in flash |
| Ingress protection | IPX65 |
| Dimensions | 94 mm diameter x 76 mm height |
3. Installation and wiring
Mount the unit with screws through the base mounting holes. The manufacturer drawing shows 4 mm holes spaced 9.1 cm apart.
RS485 version
| Conductor | Function |
|---|---|
| Red | DC positive |
| Black | DC negative |
| Yellow | RS485 A |
| Green | RS485 B |
Connect A and B to the controller or a USB-RS485 converter. Use a twisted pair and a daisy-chain bus for several units.
RS232 version. The manufacturer drawing shows red and black power conductors and a cable ending in a 9-pin D-sub connector. The manual does not give the pinout or state whether the RS232 version uses the Modbus frames in this manual. Confirm both before connecting it.
Switch-input version. The manual lists three switch inputs but gives no wiring diagram, trigger level, or trigger-mode table for this model. Obtain the delivered wiring label before connecting inputs.
4. Modbus RTU commissioning (RS485 version)
| Parameter | Factory default |
|---|---|
| Device address | 01 |
| Baud rate | 9600 bit/s |
| Data bits | 8 |
| Stop bits | 1 |
| Parity | Not stated in the manufacturer manual |
| Error checking | CRC16 (Modbus, polynomial 0xA001), low byte first |
| Default volume | 30 |
Every request is eight bytes:
text
ADDR FUNC REG_H REG_L DATA_H DATA_L CRC_L CRC_H| Field | Meaning |
|---|---|
ADDR | Device address. 0xFF is a broadcast-style super address that any unit accepts; use it only with one unit connected |
FUNC | 0x06 writes a control command; 0x03 reads a status value |
REG_H | Light state applied with a playback command; 00 for plain commands (section 5.2) |
REG_L | Command code |
DATA_H DATA_L | Command parameter |
All values in this manual are hexadecimal. The manufacturer tables show xx xx in place of the CRC, and several printed CRC values are incorrect. Always calculate the CRC for the final frame. A unit echoes each accepted control command.
5. Control commands (function 0x06)
5.1 Command table
| Command | Function | Parameter DATA_H DATA_L |
|---|---|---|
0x0F | Play a file in a folder | DATA_H folder 01-63 (01-99), DATA_L file 01-FF (001-255) |
0x10 | Loop a file in a folder | As 0x0F |
0x03 | Play by storage order | Track number 0001-0BB8 (1-3000) |
0x08 | Loop one track | Track number |
0x01 | Next track | 0000 |
0x02 | Previous track | 0000 |
0x0D | Play / resume | 0000 |
0x0E | Pause | 0000 |
0x16 | Stop | 0001 |
0x11 | Loop all tracks | 0001 on, 0000 off |
0x17 | Loop a folder | Folder 0001-0063 |
0x18 | Random playback | 0000 |
0x19 | Loop current track | 0000 on, 0001 off |
0x04 | Volume up | 0000 |
0x05 | Volume down | 0000 |
0x06 | Set volume | 0000-001E (0-30) |
0x09 | Select playback storage | 0001 USB disk, 0004 flash |
0x0B | Set baud rate | Section 7 |
0x0C | Reset | 0000 |
0xC0 | Set device address | Section 7 |
0xC2 | Light control without changing playback | Section 5.3 |
Folder names must be 01 to 99, and file names must start with 001 to 255, for example 001alarm.mp3. The folder commands support MP3 and WAV files. A volume set by command returns to the configured volume after a restart.
0x19 acts only while a track is playing. After a folder loop starts with 0x17, play, pause, next, and previous do not end the loop; send stop (0x16) to end it.
5.2 Light state with a playback command
Put a light state XY in the REG_H byte of a playback command:
text
ADDR 06 XY CMD DATA_H DATA_L CRC_L CRC_H| X | Light pattern | Y | Color |
|---|---|---|---|
1 | Steady during playback, off after playback | 1 | Red |
2 | Slow flash during playback, off after playback | 2 | Yellow |
3 | Rapid flash during playback, off after playback | 3 | Green |
4 | Steady, kept on after playback | 4 | White |
5 | Slow flash, kept on after playback | 5 | Blue |
6 | Rapid flash, kept on after playback | 6 | Cyan |
0 | Off | 7 | Purple |
0 | No light |
XY = 00 reuses the light state of the previous playback; after power-up, the lamp is off. The manufacturer examples use XY = 60 to play audio with the lamp off.
| Request (address 01) | Action |
|---|---|
01 06 31 03 00 01 B6 F6 | Play track 1 with rapid-flashing red light, off after playback |
01 06 14 0F 01 01 7C 69 | Play folder 01 file 001 with steady white light, off after playback |
01 06 47 03 00 01 AC BE | Play track 1 with steady purple light that stays on |
01 06 60 03 00 01 A6 0A | Play track 1 with the lamp off |
5.3 Independent light control (0xC2)
text
ADDR 06 00 C2 00 XY CRC_L CRC_HX is 4 steady, 5 slow flash, or 6 rapid flash; Y selects the color from the table in section 5.2. XY = 60 switches the lamp off. The lamp keeps the commanded state until another light command changes it, and the command does not change the current playback.
| Request (address 01) | Action |
|---|---|
01 06 00 C2 00 41 E8 06 | Steady red |
01 06 00 C2 00 57 69 C8 | Slow-flashing purple |
01 06 00 C2 00 64 29 DD | Rapid-flashing white |
01 06 00 C2 00 60 28 1E | Lamp off |
6. Status queries (function 0x03)
Send ADDR 03 00 CMD 00 00 CRC_L CRC_H. The response is ADDR 03 02 DH DL CRC_L CRC_H.
| Command | Query | Response |
|---|---|---|
0x3F | Online storage | DL = 08 means flash is online |
0x42 | Playback state | DL = 00 stopped, 01 playing, 02 paused |
0x43 | Current volume | DL = volume, for example 1E = 30 |
0x49 | Number of files in flash | DH DL = file count |
0x4D | Current track | DH DL = track in storage order |
0x70 | Sound and light state | See below |
0xFE | Software version | Response format not documented |
For 0x70, the response is ADDR 03 02 DH XY CRC_L CRC_H. DH is the track now playing in storage order, and DH = 00 means no audio is playing. XY uses the same light-state values as section 5.2.
Example: 01 03 02 00 12 38 49 means no audio is playing and the light state is steady yellow with playback. The reported state can differ from the actual lamp if no light state was ever commanded.
7. Address and baud-rate settings
Device address. Write the new address to command 0xC0: ADDR 06 00 C0 00 NN CRC_L CRC_H. The usable range is 01-FE (1-254). The address takes effect immediately and is retained after power-off. Configure one unit at a time.
Baud rate. Write a selector to command 0x0B:
| Selector | Baud rate (bit/s) | Selector | Baud rate (bit/s) |
|---|---|---|---|
01 | 9600 | 05 | 115200 |
02 | 19200 | 06 | 256000 |
03 | 38400 | 07 | 35250, as printed by the manufacturer; confirm before use |
04 | 57600 | 09 | 4800 |
Wait one second, then send reset (0x0C) or power-cycle the unit. The new baud rate is retained.
8. Replacing audio files
- Disconnect the unit's power supply.
- Unscrew the light cover and connect the USB-C port to a computer. The flash memory appears as a removable drive.
- Format the drive before copying new files to remove hidden files.
- Copy files one by one in the required play order. Commands
0x03and0x08use the copy order, not the file name order. - Use MP3 files at a supported sample rate: 8, 11.025, 12, 16, 22.05, 24, 32, 44.1, or 48 kHz.
- Disconnect the USB cable before powering the unit again.
9. Troubleshooting
| Symptom | Likely cause | Action |
|---|---|---|
| Indicator off, no response | No supply or wrong polarity | Check the DC voltage, polarity, and current capacity |
| Indicator steady, no audio after a play command | No valid audio file, or serial link not working | Check the files over USB; check A/B wiring, address, baud rate, and CRC |
| Indicator flashing, no audio | Unsupported audio file | Re-encode as MP3 at a supported sample rate, 192 kbps or lower |
| Audio breaks up at high volume | Supply voltage or current too low | Use at least DC 12 V with 1-2 A available |
| Wrong file plays | Copy order differs from the intended order, or hidden files remain | Format the drive and copy files again in order |
| Wrong color shown | Three-color value range used, or X outside the documented range | Use the seven-color values in sections 5.2 and 5.3 |
Inspect terminals, cable routing, mounting hardware, the light window, and sound openings during scheduled maintenance.
10. Confirmation items
- Supply range and AC 220 V availability for the ordered unit
- Serial parity on the delivered unit
- RS232 pinout and command set
- Switch-input wiring, trigger level, and trigger behavior
Source basis
- Manufacturer YX95RGB Modbus sounder-beacon manual V1.0, sections 2-8
- Supplied product catalog, page 17: YX95RGB-7S
- Product series: Industrial Audible & Visual Alarm
- Model: Y811-95AV
- Y811-95AV specification