Y402-L1-L Wireless I/O System User Manual ​

Product Introduction ​

Y402-L1-L transmits independent switch states from 1 to 20 slave transmitters to one master receiver over LoRa. Each slave has one digital input and is assigned to one of the master's 20 channel relays. The master reports the corresponding relay state back to that slave's voltage feedback output.

The master also has a summary relay: it energizes when any channel relay is on and releases when all 20 channel relays are off. For electrical ratings and dimensions, see the Y402-L1-L Specification.

Operating Logic ​

Event during normal communicationResponse
A slave input closes to input commonThe corresponding master channel relay energizes and its NO–COM contact closes. The master reports that output state to the assigned slave.
The slave receives an ON state reportIts feedback indicator turns on and its feedback output provides approximately the slave supply voltage.
The slave input opensThe corresponding master channel relay releases. When the OFF state is reported back, the feedback indicator and voltage output turn off.
Any master channel relay is onThe summary relay energizes. It releases when all channel relays are off.

For example, slaves assigned to channels 1, 6, 15 and 20 operate their respective master outputs independently. If any of those outputs is on, the summary relay is also on. The feedback indicates the state reported by the master; it does not verify that an external load has operated.

Link-loss output behavior and recovery timing are not specified in the source manual. Check the behavior of the supplied system with loads isolated before using it for control or alarms. Do not assume another Y402 model's timeout applies.

Installation and Wiring ​

Mounting and Antenna ​

Mount the modules on a 35 mm DIN rail in a stable, suitable enclosure. Keep them away from direct sunlight, heat, moisture, dust, strong interference and large metal equipment. Keep the antenna outside metal enclosures. Connect a suitable antenna before operation, mount it vertically in an open location and, where practical, approximately 2 m above ground. Tighten the antenna connector.

The stated range is up to 5 km in an open area; obstructions, interference, antenna placement and site conditions affect the installed range. The link is half-duplex and its delay varies with conditions.

Power ​

Disconnect power before wiring. Supply each master and slave from a suitable 9–36 V DC power source. Connect the positive and negative leads to the marked power terminals and check the connections before applying power. The modules include reverse-polarity protection. Maximum consumption is approximately 6.8 W for the master and 1.5 W per slave.

Slave Input ​

Connect a passive dry contact between the slave input and input common. Closing the contact activates the input. For an NPN open-collector output, connect its collector to input and its emitter or 0 V reference to input common. Power the sensor separately according to its rating.

Do not connect sensor power or a voltage-output signal directly to the input. Use an interposing relay for PNP or other powered outputs, and connect only its dry contact to input and input common. Follow the markings on the supplied device.

Dry-contact input connection

Slave Feedback Output ​

When the feedback indicator is on, the voltage between the marked feedback V+ and V- terminals is approximately equal to the slave supply voltage. When the indicator is off, the feedback output has no voltage output. A compatible DC indicator can be connected across the feedback terminals, subject to the output's permitted load.

The source manual does not specify the feedback output current rating. Confirm that rating and polarity with the supplier before connecting a load. This is a powered voltage output, not a relay contact.

Master Relay Outputs ​

The master has 20 channel relays and one summary relay. The 20 channel relays have normally open contacts; their common terminals are internally connected. Do not treat these outputs as 20 isolated circuits. Each channel relay is rated 250 V AC / 1 A or 28 V DC / 1 A.

The summary relay has normally open (NO), normally closed (NC) and common (COM) contacts and is rated 250 V AC / 5 A or 28 V DC / 5 A. When it energizes, NO–COM closes and NC–COM opens.

Relay contacts require an external load supply. Disconnect the load supply before wiring, observe both voltage and current limits, and select protection and surge suppression for the load. Use a suitably rated external contactor or power relay for inductive or larger loads. High-voltage wiring must be performed by qualified personnel.

Pairing and Configuration ​

The supplied master and slaves are paired before shipment. To add a slave or change its assigned channel, contact the supplier for the pairing wiring for your hardware before connecting the communication wires.

Once the temporary wiring has been confirmed and connected, select the channel as follows:

  1. Apply power to the master and slave.
  2. Briefly press the master pairing button. Link indicator 1 flashes. Each additional brief press advances to the next channel indicator.
  3. Select the intended channel. Pairing starts after approximately 3 seconds.
  4. Wait 30–60 seconds. A steady slave link indicator indicates successful pairing.

Follow the supplier's confirmed instructions for disconnecting the temporary wiring and verify the assigned channel with the load isolated. Record each slave's location and channel assignment.

Commissioning ​

Indicators ​

DeviceIndicatorMeaning
SlaveWorkOn when the system is operating
SlaveLinkOn when the link is established
SlaveInputOn while input and common are closed
SlaveFeedbackOn when the corresponding master output is reported on; the voltage feedback output is active
MasterWorkOn when the system is operating
MasterLink 1–20Shows the connection status of the corresponding slave
MasterOutput 1–20On when the corresponding channel NO–COM contact is closed
MasterSummary outputOn when the summary relay NO–COM contact is closed

Functional Checks ​

  1. With control loads isolated, check power polarity, antennas, input wiring, relay wiring, channel assignments and load ratings. Power the master and installed slaves.
  2. Check the master and slave work and link indicators. Open all slave inputs. For each installed slave, close its input and check that its assigned master channel output and the summary relay turn on, while the other channel outputs remain off. Open the input and check that both relays release before testing the next slave.
  3. Check that the slave feedback indicator follows the master-reported channel state. Check the feedback output voltage using an appropriate meter; do not connect a feedback load until its permitted current is confirmed.
  4. Activate more than one slave input. Confirm that each corresponding master output operates and that the summary relay is on. Release the inputs one at a time and confirm the summary relay releases only after all channel relays are off.
  5. At the installed locations, check communication and evaluate link-loss and recovery behavior with loads isolated. Confirm the result is suitable for the application before connecting control loads.

Troubleshooting ​

SymptomChecks
No work indicatorCheck supply voltage, polarity, connections and the power source at the affected module.
Slave link indicator is offCheck power, antenna connections and placement, obstructions, interference and the slave's pairing and channel assignment.
Input indicator does not turn onCheck the passive contact or NPN connection between input and input common. Do not apply a voltage signal to the input.
Wrong master channel operatesCheck the slave's assigned channel and repeat pairing only with confirmed pairing wiring.
Master output turns on but slave feedback does notCheck the link and feedback indicator, then check the feedback terminals and supply. Confirm the feedback output load rating.
Relay operates but the load does notCheck the external supply, NO/COM/NC selection, shared common, wiring, protection and load ratings.

Safety Notes ​

  • Keep liquid away from the modules; do not install them in flammable or explosive locations.
  • Do not exceed output ratings or dismantle the modules.
  • The half-duplex link has variable delay. Do not use it as the sole emergency-stop or personnel-safety path, or where guaranteed real-time response is required.
  • The source manual does not specify the link-loss state. Validate the complete installation and its failure behavior for the intended application.