Appearance
Y402-L1-L 20-Channel LoRa Wireless I/O System Specification
Overview
The Y402-L1-L carries independent switch states from 1 to 20 slaves to one master over a private LoRa link. Each slave has one digital input. The master has 20 channel relay outputs. Each slave is assigned to one master channel, and its input controls the corresponding relay output. Each slave also provides a voltage output that reflects the state reported by its corresponding master relay.
The master has an additional summary relay. It energizes when any of the 20 channel relays is on and releases when all are off. The system is half-duplex; wireless delay varies with site conditions and it is not intended for applications requiring a high degree of real-time response.
Model and Ordering
In Y402-L1-L, the first L denotes 20 channels, 1 denotes one input per slave, and the final L denotes LoRa. Select one master and the required number of slaves, from 1 to 20. Confirm the antenna and operating frequency for the installation when ordering.
Wireless and General Specifications
| Parameter | Specification |
|---|---|
| Communication | LoRa, half-duplex |
| Range | Up to 5,000 m in an open area; actual range depends on antenna installation, obstructions and interference |
| Antenna connector | SMA female, external thread and center socket |
| Antenna | 470 MHz antenna; specified operating band 398–525 MHz |
| Power supply | 9–36 V DC for master and slave; reverse-polarity protection |
| Operating temperature | -20 to +85 °C |
| Operating humidity | 10–90% RH, non-condensing |
| Mounting | 35 mm DIN rail |
Slave Transmitter
| Parameter | Specification |
|---|---|
| Digital input | 1 dry-contact or NPN input; close input to common to activate |
| Feedback output | Voltage approximately equal to the slave supply when the feedback indicator is on; no output voltage when off |
| Maximum power consumption | Approx. 1.5 W |
| Dimensions | 103 × 54 × 32 mm |
| Weight | Approx. 140 g |
The feedback indicates the corresponding master output state reported back to the slave. It is a voltage output, not a dry relay contact. The source documentation does not specify its output current rating; confirm the permitted load before connecting one.
Master Receiver
| Parameter | Specification |
|---|---|
| Channel outputs | 20 normally open relay outputs, each rated 250 V AC / 1 A or 28 V DC / 1 A |
| Channel output common | The 20 channel relay common terminals are internally connected |
| Summary output | 1 changeover relay, normally open, normally closed and common; 250 V AC / 5 A or 28 V DC / 5 A |
| Maximum power consumption | Approx. 6.8 W |
| Dimensions | 160 × 95 × 56 mm |
| Weight | Approx. 380 g |
The relay contacts require a suitable external supply for the load. Select protection and a contactor appropriate to the load, particularly for inductive loads. The channel outputs share a common connection; do not assume 20 isolated relay circuits.
Installation and Pairing
- Connect a passive switch between the slave input and common. For an NPN open-collector signal, connect the collector to input and the emitter or 0 V reference to input common. Power the sensor separately according to its rating. Use an interposing relay to convert an active voltage signal to a dry contact.
- Master and supplied slaves are paired before shipment. Additional slaves or channel assignments require pairing. For pairing instructions, see the user manual.
- Mount the antenna vertically in an open location, approximately 2 m above ground where practical, and away from large metal objects. Do not install it inside a metal enclosure.
- Link-loss output behavior and recovery timing are not specified in the source manual. Verify them on the supplied hardware before relying on the system for control or alarms. Do not use the wireless link as the sole personnel-safety or emergency-stop path.
- Manufacturer: Hunan YenGear Tech Co., Ltd.
- Email: [email protected]
- Website: www.yengear.com