Y402-L1-L 20-Channel LoRa Wireless I/O System Specification ​

Overview ​

The Y402-L1-L carries independent switch states from 1 to 20 slaves to one master over a private LoRa link. Each slave has one digital input. The master has 20 channel relay outputs. Each slave is assigned to one master channel, and its input controls the corresponding relay output. Each slave also provides a voltage output that reflects the state reported by its corresponding master relay.

The master has an additional summary relay. It energizes when any of the 20 channel relays is on and releases when all are off. The system is half-duplex; wireless delay varies with site conditions and it is not intended for applications requiring a high degree of real-time response.

Model and Ordering ​

In Y402-L1-L, the first L denotes 20 channels, 1 denotes one input per slave, and the final L denotes LoRa. Select one master and the required number of slaves, from 1 to 20. Confirm the antenna and operating frequency for the installation when ordering.

Wireless and General Specifications ​

ParameterSpecification
CommunicationLoRa, half-duplex
RangeUp to 5,000 m in an open area; actual range depends on antenna installation, obstructions and interference
Antenna connectorSMA female, external thread and center socket
Antenna470 MHz antenna; specified operating band 398–525 MHz
Power supply9–36 V DC for master and slave; reverse-polarity protection
Operating temperature-20 to +85 °C
Operating humidity10–90% RH, non-condensing
Mounting35 mm DIN rail

Slave Transmitter ​

ParameterSpecification
Digital input1 dry-contact or NPN input; close input to common to activate
Feedback outputVoltage approximately equal to the slave supply when the feedback indicator is on; no output voltage when off
Maximum power consumptionApprox. 1.5 W
Dimensions103 × 54 × 32 mm
WeightApprox. 140 g

The feedback indicates the corresponding master output state reported back to the slave. It is a voltage output, not a dry relay contact. The source documentation does not specify its output current rating; confirm the permitted load before connecting one.

Master Receiver ​

ParameterSpecification
Channel outputs20 normally open relay outputs, each rated 250 V AC / 1 A or 28 V DC / 1 A
Channel output commonThe 20 channel relay common terminals are internally connected
Summary output1 changeover relay, normally open, normally closed and common; 250 V AC / 5 A or 28 V DC / 5 A
Maximum power consumptionApprox. 6.8 W
Dimensions160 × 95 × 56 mm
WeightApprox. 380 g

The relay contacts require a suitable external supply for the load. Select protection and a contactor appropriate to the load, particularly for inductive loads. The channel outputs share a common connection; do not assume 20 isolated relay circuits.

Installation and Pairing ​

  • Connect a passive switch between the slave input and common. For an NPN open-collector signal, connect the collector to input and the emitter or 0 V reference to input common. Power the sensor separately according to its rating. Use an interposing relay to convert an active voltage signal to a dry contact.
  • Master and supplied slaves are paired before shipment. Additional slaves or channel assignments require pairing. For pairing instructions, see the user manual.
  • Mount the antenna vertically in an open location, approximately 2 m above ground where practical, and away from large metal objects. Do not install it inside a metal enclosure.
  • Link-loss output behavior and recovery timing are not specified in the source manual. Verify them on the supplied hardware before relying on the system for control or alarms. Do not use the wireless link as the sole personnel-safety or emergency-stop path.