Y812 — Industrial Audible & Visual Alarm Technical Manual
This manual applies to the Y812-AV public model and its three configurations:
- 02K
- 04K
- 05K
All three configurations use the same Modbus RTU command set. Use the model specification as the authority for the ordered enclosure, power, and protection.
Contents
- Safety and scope
- Configuration selection
- Installation
- Communication commissioning
- Trigger inputs
- Optional functions
- Troubleshooting
- Confirmation checklist
1. Safety and scope
Y812 products provide auxiliary audible and visual warning for industrial equipment and sites. They are not a substitute for an emergency-stop circuit, a certified fire-alarm panel, a life-safety system, or a safety-rated control circuit.
The manufacturer manuals cover DC 12-24 V versions. Do not connect AC power or more than 24 V to a DC version. The catalog also lists AC 220 V versions; a qualified electrician must install them. Disconnect all power before opening the beacon cover or changing power or communication wiring.
2. Configuration selection
| Configuration | Audio output | Memory | Protection | Enclosure and mounting |
|---|---|---|---|---|
| 02K | 15 W at 12 V, 30 W at 24 V (6 Ω) | 4 MB | IPX65 | Rectangular metal enclosure, 360 x 182 x 100 mm |
| 04K | 15 W at 12 V, 30 W at 24 V (6 Ω) | 4 MB | IPX65 | Trapezoid metal enclosure, side brackets with 23 cm hole spacing |
| 05K | 25 W at 12 V, 50 W at 24 V (4 Ω) | 8 MB | IP65 | Wall plate with 16.6 cm horizontal hole spacing, 30 cm height |
Keep the configuration visible on the purchase order and service record. The command set is shared, but power, memory, enclosure, and protection differ. The catalog lists different memory, protection, and interface values; see the specification.
3. Installation
3.1 Preparation
- Confirm the configuration and the supply voltage on the label.
- Select a DC supply and cable size for the audio power. Use 24 V when full output is required.
- Confirm the mounting holes for the configuration.
- Disconnect all power before wiring.
3.2 Wiring
| Conductor | Function |
|---|---|
| Yellow | RS485 A+ |
| Green | RS485 B- |
| Power pair | DC positive and negative, as labeled on the delivered cable |
The manufacturer manuals state the RS485 colors in the factory defaults but do not include a wiring drawing or power-wire colors. Confirm the label on the delivered cable before energizing. Allow for startup and alarm-state current when selecting the supply; the manuals do not state complete-unit current.
3.3 Mounting and protection
Mount the enclosure on a rigid surface with the brackets or wall plate. Use the marking on the delivered unit for the protection rating; do not apply one configuration's rating to another. Seal cable entries so that the rating is preserved, and do not drill or modify the housing without a design review.
4. Communication commissioning
4.1 Commissioning sequence
- Connect only one device to the controller.
- Set the controller to 9600 bit/s, 8 data bits, 1 stop bit, and the parity confirmed for the delivered unit.
- Send one documented command and confirm the echo, light, and sound response.
- Set a unique address and record it with the communication settings.
- Add further devices only after each address is verified.
Do not copy a Y811 light-control map to Y812. Y812 has a single-color beacon, and its light values differ from every Y811 model.
4.2 Modbus RTU protocol
Serial defaults. Address 01, 9600 bit/s, 8 data bits, 1 stop bit, CRC16 (Modbus, low byte first). Parity is not stated. RS485 wiring is yellow A+ and green B-. Default volume is 30 of 30 levels.
Frame. Every request is ADDR FUNC REG_H REG_L DATA_H DATA_L CRC_L CRC_H. Function 0x06 writes a command and 0x03 reads a status value. REG_L is the command code and REG_H carries a lamp state for playback commands. Address 0xFF is accepted by any unit; use it only with one unit connected. All values are hexadecimal; calculate the CRC for every frame.
Control commands (function 0x06).
| Command | Function | Parameter DATA_H DATA_L |
|---|---|---|
0x0F | Play a file in a folder | DATA_H folder 01-63, DATA_L file 01-FF |
0x10 | Loop a file in a folder | As 0x0F |
0x03 | Play by storage order | Track number |
0x08 | Loop one track | Track number |
0x01 / 0x02 | Next / previous track | 0000 |
0x0D / 0x0E | Play / pause | 0000 |
0x16 | Stop; also switches off a lamp started by 0xC2 | 0001 |
0x11 | Loop all tracks | 0001 on, 0000 off |
0x17 | Loop a folder | Folder number |
0x18 | Random playback | 0000 |
0x19 | Loop current track | 0000 on, 0001 off |
0x04 / 0x05 | Volume up / down | 0000 |
0x06 | Set volume | 0000-001E (0-30) |
0x09 | Select playback storage | 0001 USB disk, 0004 flash |
0x0B | Set baud rate | 01 9600, 02 19200, 03 38400, 04 57600, 05 115200, 06 256000, 09 4800 |
0x0C | Reset | 0000 |
0xC0 | Set device address | 0001-00FE; takes effect immediately and is retained |
0xC2 | Lamp control without audio | See below |
0xCA | Command acknowledgement | 0000 off, 0001 on (default); listed in only one supplied 04K manual |
After a baud-rate change, wait one second, then send reset or power-cycle the unit.
0xCA switches off the echo that the unit sends for each accepted control command. Queries still respond. Use it when many units on one bus make the echoes unreliable. Only one of the supplied 04K manuals lists it, and the 02K and 05K manuals do not; confirm support on the delivered firmware before relying on it.
Lamp state with a playback command. Put one of these values in REG_H:
REG_H | Lamp during playback | Lamp after playback |
|---|---|---|
00 | Rapid flash | Off |
10 | Slow flash | Off |
20 | Steady | Off |
30 | Rapid flash | Keeps rapid flash |
40 | Slow flash | Keeps slow flash |
50 | Steady | Keeps steady |
60 | Off | Off |
For example, 01 06 30 0F 01 01 76 99 plays folder 01 file 001 and leaves the lamp flashing rapidly after playback. 01 06 60 03 00 00 67 CA switches the lamp off.
Independent lamp control (0xC2). ADDR 06 00 C2 00 DL CRC_L CRC_H, where DL is 03 rapid flash, 04 slow flash, 05 steady, or 06 off. The lamp keeps the state until it receives another lamp command or stop (0x16). Example: 01 06 00 C2 00 05 E8 35 turns the lamp on steadily.
Status queries (function 0x03). Send ADDR 03 00 CMD 00 00 CRC_L CRC_H; the response is ADDR 03 02 DH DL CRC_L CRC_H.
| Command | Query | Response |
|---|---|---|
0x3F | Online storage | DL = 08 means flash is online |
0x42 | Playback state | DL = 00 stopped, 01 playing, 02 paused |
0x43 | Volume | DL = volume |
0x49 | Number of files | DH DL = file count |
0x4D | Current track | DH DL = track in storage order |
0x70 | Sound and lamp state | DH = track playing, 00 when silent; DL = lamp state below |
0xFE | Software version | Response format not documented |
0x70 DL | Lamp state | 0x70 DL | Lamp state |
|---|---|---|---|
00 | Rapid flash with playback | 04 | Continuous slow flash |
01 | Slow flash with playback | 05 | Continuous steady |
02 | Steady with playback | 06 | Off |
03 | Continuous rapid flash |
"With playback" states follow the audio and switch off when playback ends. Continuous states stay on regardless of playback. Example: 01 03 02 00 03 F8 45 means no audio is playing and the lamp is flashing rapidly.
Configuration file. A single .txt file in the root of the audio memory can hold five digits: digit 1 is 0, digits 2-3 set the retained volume (01-30, default 30), and digits 4-5 set the RS485 address (00-99, default 01). An address in the file takes priority over the command. Never store more than one configuration file.
Audio files. Power off the unit, unscrew the beacon cover, and connect the Micro USB port to a computer; the flash appears as a removable drive. Format the drive, then copy MP3 files one by one in play order. Supported sample rates are 8, 11.025, 12, 16, 22.05, 24, 32, 44.1, and 48 kHz. Folders are named 01-99 and files start with 001-255. Disconnect the USB cable before powering the unit again.
5. Trigger inputs
The manufacturer manuals document Modbus RTU control only and do not describe trigger inputs. The catalog lists six switch inputs for 02K and 04K and four for 05K. Treat switch inputs as an order option that must be confirmed, together with the electrical input type, common terminal, active state, and isolation, before connecting any input.
6. Optional functions
The catalog lists microwave sensing, a dual-beam infrared sensor, and remote control as options for the 05K configuration. The microwave-sensor version has an adjustable detection distance of 2-10 m and can sense all day or at night only. Treat these as ordered configuration options, not as standard functions of every Y812-AV unit.
Confirm the following before commissioning an option:
- Sensor model and supply
- Detection range and adjustment
- Trigger priority when both communication and sensor inputs are active
- Remote-control channel and operating distance
- Fail-safe behavior after communication or power loss
7. Troubleshooting
| Symptom | Likely cause | Action |
|---|---|---|
| Indicator off, unit does not start | No supply, wrong polarity, or wrong voltage | Check the label, DC voltage, polarity, and current capacity |
| No echo after a control command | Wrong A/B, address, baud rate, or CRC; or acknowledgement switched off by 0xCA | Check settings against section 4.2 and send a query, which always responds |
| Indicator steady, no audio after a play command | No valid audio file | Check the files over USB and copy them again in order |
| Indicator flashing, no audio | Unsupported audio file | Re-encode as MP3 at a supported sample rate, 192 kbps or lower |
| Audio breaks up at high volume | Supply voltage or current too low | Use 24 V and a supply rated for the audio power |
| Wrong file plays | Copy order differs from the intended order, or hidden files remain | Format the drive and copy files again in order |
| Enclosure shows water ingress | Cable entry or mounting damaged | Power off, inspect the seal, and restore the rated installation |
| 05K option does not trigger | Sensor or remote option is absent or misconfigured | Confirm the ordered option and its wiring |
8. Confirmation checklist
Before publishing a final installation drawing or software driver, confirm:
- Configuration: 02K, 04K, or 05K
- Supply option and complete-unit current; AC 220 V versions are not covered by the manuals
- Serial parity on the delivered unit
0xCAacknowledgement support on the delivered firmware- RS232 and switch-input versions listed in the catalog
- Final wire colors, enclosure drawing, cable entry, and IP marking
- Optional sensor or remote-control configuration for 05K
Source basis
- Manufacturer YX02K Modbus RTU sounder-beacon manual V1.3: 02K
- Manufacturer YX04K Modbus RTU sounder-beacon manual V1.3 (two supplied copies): 04K
- Manufacturer YX05K Modbus RTU sounder-beacon manual V1.0: 05K
- Supplied product catalog, pages 19-20
- Product series: Industrial Audible & Visual Alarm
- Model: Y812-AV
- Configurations: 02K, 04K, 05K
- Y812-AV specification