Y812 — Industrial Audible & Visual Alarm Technical Manual ​

This manual applies to the Y812-AV public model and its three configurations:

  • 02K
  • 04K
  • 05K

All three configurations use the same Modbus RTU command set. Use the model specification as the authority for the ordered enclosure, power, and protection.

Contents ​

  1. Safety and scope
  2. Configuration selection
  3. Installation
  4. Communication commissioning
  5. Trigger inputs
  6. Optional functions
  7. Troubleshooting
  8. Confirmation checklist

1. Safety and scope ​

Y812 products provide auxiliary audible and visual warning for industrial equipment and sites. They are not a substitute for an emergency-stop circuit, a certified fire-alarm panel, a life-safety system, or a safety-rated control circuit.

The manufacturer manuals cover DC 12-24 V versions. Do not connect AC power or more than 24 V to a DC version. The catalog also lists AC 220 V versions; a qualified electrician must install them. Disconnect all power before opening the beacon cover or changing power or communication wiring.

2. Configuration selection ​

ConfigurationAudio outputMemoryProtectionEnclosure and mounting
02K15 W at 12 V, 30 W at 24 V (6 Ω)4 MBIPX65Rectangular metal enclosure, 360 x 182 x 100 mm
04K15 W at 12 V, 30 W at 24 V (6 Ω)4 MBIPX65Trapezoid metal enclosure, side brackets with 23 cm hole spacing
05K25 W at 12 V, 50 W at 24 V (4 Ω)8 MBIP65Wall plate with 16.6 cm horizontal hole spacing, 30 cm height

Keep the configuration visible on the purchase order and service record. The command set is shared, but power, memory, enclosure, and protection differ. The catalog lists different memory, protection, and interface values; see the specification.

3. Installation ​

3.1 Preparation ​

  1. Confirm the configuration and the supply voltage on the label.
  2. Select a DC supply and cable size for the audio power. Use 24 V when full output is required.
  3. Confirm the mounting holes for the configuration.
  4. Disconnect all power before wiring.

3.2 Wiring ​

ConductorFunction
YellowRS485 A+
GreenRS485 B-
Power pairDC positive and negative, as labeled on the delivered cable

The manufacturer manuals state the RS485 colors in the factory defaults but do not include a wiring drawing or power-wire colors. Confirm the label on the delivered cable before energizing. Allow for startup and alarm-state current when selecting the supply; the manuals do not state complete-unit current.

3.3 Mounting and protection ​

Mount the enclosure on a rigid surface with the brackets or wall plate. Use the marking on the delivered unit for the protection rating; do not apply one configuration's rating to another. Seal cable entries so that the rating is preserved, and do not drill or modify the housing without a design review.

4. Communication commissioning ​

4.1 Commissioning sequence ​

  1. Connect only one device to the controller.
  2. Set the controller to 9600 bit/s, 8 data bits, 1 stop bit, and the parity confirmed for the delivered unit.
  3. Send one documented command and confirm the echo, light, and sound response.
  4. Set a unique address and record it with the communication settings.
  5. Add further devices only after each address is verified.

Do not copy a Y811 light-control map to Y812. Y812 has a single-color beacon, and its light values differ from every Y811 model.

4.2 Modbus RTU protocol ​

Serial defaults. Address 01, 9600 bit/s, 8 data bits, 1 stop bit, CRC16 (Modbus, low byte first). Parity is not stated. RS485 wiring is yellow A+ and green B-. Default volume is 30 of 30 levels.

Frame. Every request is ADDR FUNC REG_H REG_L DATA_H DATA_L CRC_L CRC_H. Function 0x06 writes a command and 0x03 reads a status value. REG_L is the command code and REG_H carries a lamp state for playback commands. Address 0xFF is accepted by any unit; use it only with one unit connected. All values are hexadecimal; calculate the CRC for every frame.

Control commands (function 0x06).

CommandFunctionParameter DATA_H DATA_L
0x0FPlay a file in a folderDATA_H folder 01-63, DATA_L file 01-FF
0x10Loop a file in a folderAs 0x0F
0x03Play by storage orderTrack number
0x08Loop one trackTrack number
0x01 / 0x02Next / previous track0000
0x0D / 0x0EPlay / pause0000
0x16Stop; also switches off a lamp started by 0xC20001
0x11Loop all tracks0001 on, 0000 off
0x17Loop a folderFolder number
0x18Random playback0000
0x19Loop current track0000 on, 0001 off
0x04 / 0x05Volume up / down0000
0x06Set volume0000-001E (0-30)
0x09Select playback storage0001 USB disk, 0004 flash
0x0BSet baud rate01 9600, 02 19200, 03 38400, 04 57600, 05 115200, 06 256000, 09 4800
0x0CReset0000
0xC0Set device address0001-00FE; takes effect immediately and is retained
0xC2Lamp control without audioSee below
0xCACommand acknowledgement0000 off, 0001 on (default); listed in only one supplied 04K manual

After a baud-rate change, wait one second, then send reset or power-cycle the unit.

0xCA switches off the echo that the unit sends for each accepted control command. Queries still respond. Use it when many units on one bus make the echoes unreliable. Only one of the supplied 04K manuals lists it, and the 02K and 05K manuals do not; confirm support on the delivered firmware before relying on it.

Lamp state with a playback command. Put one of these values in REG_H:

REG_HLamp during playbackLamp after playback
00Rapid flashOff
10Slow flashOff
20SteadyOff
30Rapid flashKeeps rapid flash
40Slow flashKeeps slow flash
50SteadyKeeps steady
60OffOff

For example, 01 06 30 0F 01 01 76 99 plays folder 01 file 001 and leaves the lamp flashing rapidly after playback. 01 06 60 03 00 00 67 CA switches the lamp off.

Independent lamp control (0xC2). ADDR 06 00 C2 00 DL CRC_L CRC_H, where DL is 03 rapid flash, 04 slow flash, 05 steady, or 06 off. The lamp keeps the state until it receives another lamp command or stop (0x16). Example: 01 06 00 C2 00 05 E8 35 turns the lamp on steadily.

Status queries (function 0x03). Send ADDR 03 00 CMD 00 00 CRC_L CRC_H; the response is ADDR 03 02 DH DL CRC_L CRC_H.

CommandQueryResponse
0x3FOnline storageDL = 08 means flash is online
0x42Playback stateDL = 00 stopped, 01 playing, 02 paused
0x43VolumeDL = volume
0x49Number of filesDH DL = file count
0x4DCurrent trackDH DL = track in storage order
0x70Sound and lamp stateDH = track playing, 00 when silent; DL = lamp state below
0xFESoftware versionResponse format not documented
0x70 DLLamp state0x70 DLLamp state
00Rapid flash with playback04Continuous slow flash
01Slow flash with playback05Continuous steady
02Steady with playback06Off
03Continuous rapid flash

"With playback" states follow the audio and switch off when playback ends. Continuous states stay on regardless of playback. Example: 01 03 02 00 03 F8 45 means no audio is playing and the lamp is flashing rapidly.

Configuration file. A single .txt file in the root of the audio memory can hold five digits: digit 1 is 0, digits 2-3 set the retained volume (01-30, default 30), and digits 4-5 set the RS485 address (00-99, default 01). An address in the file takes priority over the command. Never store more than one configuration file.

Audio files. Power off the unit, unscrew the beacon cover, and connect the Micro USB port to a computer; the flash appears as a removable drive. Format the drive, then copy MP3 files one by one in play order. Supported sample rates are 8, 11.025, 12, 16, 22.05, 24, 32, 44.1, and 48 kHz. Folders are named 01-99 and files start with 001-255. Disconnect the USB cable before powering the unit again.

5. Trigger inputs ​

The manufacturer manuals document Modbus RTU control only and do not describe trigger inputs. The catalog lists six switch inputs for 02K and 04K and four for 05K. Treat switch inputs as an order option that must be confirmed, together with the electrical input type, common terminal, active state, and isolation, before connecting any input.

6. Optional functions ​

The catalog lists microwave sensing, a dual-beam infrared sensor, and remote control as options for the 05K configuration. The microwave-sensor version has an adjustable detection distance of 2-10 m and can sense all day or at night only. Treat these as ordered configuration options, not as standard functions of every Y812-AV unit.

Confirm the following before commissioning an option:

  • Sensor model and supply
  • Detection range and adjustment
  • Trigger priority when both communication and sensor inputs are active
  • Remote-control channel and operating distance
  • Fail-safe behavior after communication or power loss

7. Troubleshooting ​

SymptomLikely causeAction
Indicator off, unit does not startNo supply, wrong polarity, or wrong voltageCheck the label, DC voltage, polarity, and current capacity
No echo after a control commandWrong A/B, address, baud rate, or CRC; or acknowledgement switched off by 0xCACheck settings against section 4.2 and send a query, which always responds
Indicator steady, no audio after a play commandNo valid audio fileCheck the files over USB and copy them again in order
Indicator flashing, no audioUnsupported audio fileRe-encode as MP3 at a supported sample rate, 192 kbps or lower
Audio breaks up at high volumeSupply voltage or current too lowUse 24 V and a supply rated for the audio power
Wrong file playsCopy order differs from the intended order, or hidden files remainFormat the drive and copy files again in order
Enclosure shows water ingressCable entry or mounting damagedPower off, inspect the seal, and restore the rated installation
05K option does not triggerSensor or remote option is absent or misconfiguredConfirm the ordered option and its wiring

8. Confirmation checklist ​

Before publishing a final installation drawing or software driver, confirm:

  • Configuration: 02K, 04K, or 05K
  • Supply option and complete-unit current; AC 220 V versions are not covered by the manuals
  • Serial parity on the delivered unit
  • 0xCA acknowledgement support on the delivered firmware
  • RS232 and switch-input versions listed in the catalog
  • Final wire colors, enclosure drawing, cable entry, and IP marking
  • Optional sensor or remote-control configuration for 05K

Source basis ​

  • Manufacturer YX02K Modbus RTU sounder-beacon manual V1.3: 02K
  • Manufacturer YX04K Modbus RTU sounder-beacon manual V1.3 (two supplied copies): 04K
  • Manufacturer YX05K Modbus RTU sounder-beacon manual V1.0: 05K
  • Supplied product catalog, pages 19-20

  • Product series: Industrial Audible & Visual Alarm
  • Model: Y812-AV
  • Configurations: 02K, 04K, 05K
  • Y812-AV specification